background image

 

iBootBar 

 

   

Page 18 

ibootbar_v1.2x 

 

  

AutoPing 

The AutoPing feature allows iBootBar to automatically detect failed equipment and perform a timed reboot or other power 
control function (like turning on an indicator or siren).  You set any IP address to be periodically pinged.  When iBootBar no 
longer detects a response from the address, the programmed power control function is actuated. 
 
Up to eight IP addresses can be monitored by AutoPing.  Each AutoPing monitor is assigned to an outlet. 
 

Ping Address

  Enter the IP address of the device to be pinged.   

 

Ping Frequency

  Enter 1 to 999 seconds.  The ping will go out to the selected device this often. 

 

Fail Counter

  Enter 1-99 times the ping needs to fail consecutively before the selected action is taken.  When the fail count 

has been reached, the AutoPing action will be triggered. 
 

Action:

  Select from 

None

 

AutoPing not used

 

On – Latch

 

Upon triggering, iBootBar will power on the assigned outlet and remain so until 
changed via the web or telnet/serial interface.

 

On – Follow

 

Upon triggering, iBootBar will power on the assigned outlet.  When the ping 
response returns, iBootBar will power the off the outlet

 

Off – Latch

 

Upon triggering, iBootBar will power off the assigned outlet and remain so until 
changed via the web or telnet/serial interface.

 

Off – Follow

 

Upon triggering, iBootBar will power off the assigned outlet.  When the ping 
response returns, iBootBar will power the outlet on.

 

Cycle

 

Upon triggering, iBootBar will cycle the power to the assigned outlet.  iBootBar 
will wait the Ping Frequency x Fail Count; if the response does not return, the 
power will be recycled again.  This will continue until the ping response returns 
or AutoPing is turned off.  Make sure your AutoPing frequency x Fail Count is 
longer than the time required to reboot your device.

 

Cycle Once

 

Upon triggering, iBootBar will cycle power one time. It will not cycle again 
automatically until the ping response returns and is lost again.

 

 

With AutoPing operational, the iBootBar page will display the current status of this feature.  The status will be OK to 
indicate that iBootBar is receiving responses to the ping, or that the fail counter has not yet been exceeded.  Click on the 
Status message to see greater details on the AutoPing status. 
 
If the fail count has been exceeded, the status will change to Triggered.  Click on the Status message to see greater details 
on the AutoPing status. 

SSL 

The iBootBar can provide Secure Socket Layer (SSL) encryption on the web interface.  Enable this feature using the set 
web ssl yes command from the Telnet / Serial interface. 
 

Certificate Upload Utility 

The Certificate Upload Utility (CUU.exe) is designed to create and distribute Secure Socket Layer (SSL) certificates to 
iBootBars and the PCs that communicate them. Although the iBootBar comes from the factory with a certificate installed, 
this certificate common name is Dataprobe iBB, and will generate a warning message when connecting to the iBootBar 
when using SSL. For most customers, this error message can be easily ignored and secure connection to the iBootBar 

continues. 

For customers with special circumstances, the CUU was designed to facilitate creation 

and distribution of SSL Certificates tailored to a specific iBootBar, eliminating the error message entirely.

 

 

The CUU is available on the ibootbar CD or from the Dataprobe website: http://Dataprobe.com/ibootbartools.html   

Summary of Contents for iBootBar

Page 1: ...trol iBB N20 M NEMA 20 Amp 8 x NEMA 5 15 IP Control Serial Control Internal Modem iBB 2N20 2 x NEMA 40 Amp 8 x NEMA 5 15 IP Control Serial Control iBB 2N20 M 2 x NEMA 40 Amp 8 x NEMA 5 15 IP Control Serial Control Internal Modem iBB C10 IEC C14 10 Amp 8 x IEC C13 IP Control Serial Control iBB C10 M IEC C14 10 Amp 8 x IEC C13 IP Control Serial Control Internal Modem iBB 2C10 2 x IEC C14 20 Amp 8 x ...

Page 2: ...terface Basic Operation 10 Web Interface User Privileges Grouping Outlets Command Line Interface Internal Modem Advanced Operations 17 DTMF Control AutoPing SSL Certificate Utility Email Notification SNMP Firmware Upgrades Password Recovery Setup Control Center Utility Appendices 20 Specifications Compliance Modem Certifications SNMP MIB Technical Support Returns Warranty ...

Page 3: ...the grounding type plug Do not use a 3 to 2 prong adapter at the receptacle use of this type adapter may result in risk of electrical shock and or damage to this product 9 Do not allow anything to rest on the power cord Do not locate this product where the cord will be abused by persons walking on it 10 Do not overload wall outlets and extension cords as this can result in the risk of fire or elec...

Page 4: ...8 Independently controllable outlets Dual power inputs for redundant power feeds Support for dual redundant powered devices Naming of outlets for easy identification Grouping of outlets for simultaneous management Time and Date event based control of outlets Current monitoring with over and under alarm notification Multiple users with assigned rights and simultaneous control Web Browser Control Te...

Page 5: ...nch rack Ethernet The iBootBar has a 10 100 Ethernet port The default address is 192 168 0 254 Serial Port The iBootBar has a 9 pin D subminiature connector for RS 232 serial control The connector is configured as DCE for direct connection to a laptop or other terminal device Default serial parameters are 115 200 bps 8 data no parity 1 stop bit 115200 8 n 1 Serial Port pinout Pin No Description 1 ...

Page 6: ...tlets cannot exceed 12 Amps at 115VAC or 10 Amps when used at 240VAC The iBB 2C10 M is for international applications and can be used on 100V to 240VAC The iBB 2C10 provides two IEC 320 style universal inlets for connecting a detachable power cord Two standard IEC to CEE7 European cord sets are supplied with the unit for use on 10 Amp 240VAC service The total maximum current load for outlets on an...

Page 7: ...existing configurations from installed iBootBars 4 Save existing configurations for later use or as backup 5 Open saved configurations for change management 6 Clone saved configurations for replication of similar configurations in multiple iBootBars 7 Upload modified configurations to iBootBars 8 Control Power Outlets on one or more iBootBars throughout the network The iBootBar Setup and Control u...

Page 8: ...d decimal ex 192 168 0 125 set subnet dotted decimal ex 255 255 255 0 set gateway dotted decimal ex 192 168 0 2 If you wish to prevent DHCP or ARP Ping from altering the IP Address also enter the following command set ipmode static Changing any of these values will require a reboot of the unit Type the command reboot as indicated press the reset pushbutton on the front panel or remove and restore ...

Page 9: ...MAC addr 4 Ping the iBootBar to program the IP address into the iBootBar Type ping IP Address Note If the ping command returns host not responding 4 times then the address has not been programmed properly Check the IP or MAC Address for typographical errors Repeat step 2 If the problem persists contact the Dataprobe Tech Support 5 Delete the entry from the ARP cache by typing arp d IP Address 6 Pi...

Page 10: ...Device Name assigned to it in setup Two buttons on the Header allow control of the iBootBar either by individual outlets or by user assigned groups Status The Status panel displays the current state of each outlet and provides a checkbox for each outlet to allow for selection for the next outlet change activity The bottom of the Status panel shows the current draw of the A C inputs In iBootBars wi...

Page 11: ...tlets Refresh provides an update of the status page to display current outlet conditions Logout terminates the session Web Operation To operate any outlet select it with the checkbox associated with that outlet and then click the On Off or Cycle button as required The page will reload with the current status If multiple outlets are selected the page will refresh several times until all outlets hav...

Page 12: ...mands require administrative rights get current alarm set main a b highalarm nn n set main a b lowalarm nn n High and Low alarms are used to monitor current conditions and send an alert by email or SNMP when the high or low thresholds are exceeded From 0 0 to 15 0 20 0 in 20 amp units in 0 0 amp increments Main A and Main B are set separately but displayed together with the get command get console...

Page 13: ...utoping count 1 99 Set the number of failures to respond to ping before the AutoPing feature is triggered Timed Event Commands Description add event name The default time and date will be the time and date that the event is added The default action is none and the default repeat is never del event name This command removes a scheduled event from the event list This command functions the same as th...

Page 14: ...splay current web enable web port and ssl enable parameters ß set web enable yes no Enable or Disable the Web Server ß set web port 1 65535 Change the Web Server IP port ß set web ssl yes no Select SSL security for the Web Server Setting to yes requires https access and defaults port to SSL standard 443 Setting to no requires http access and defaults port to HTTP standard 80 get telnet Display cur...

Page 15: ...current time set time server dotted decimal set time usents yes no set time zone time zone 12 to 13 set time hour 0 23 set time minute 0 59 set time day 1 31 set time month 1 12 set time year 2006 2047 Set the time manually or use a time server If a timeserver is used provide the time zone offset ß Reboot is required for these settings to take effect reboot command reset button or power cycle unit...

Page 16: ...nistrator privileges set user name password newpass confirm Sets a user s password default is same as name set user name email email address 64 char max Sets a users email address set user name sendmail yes no Enables or Disables a user s receipt of email notifications set user name pin pin 0 4 10 digits for DTMF control via modem Each user s pin must be unique set to 0 to clear dtmf control Group...

Page 17: ...ed the iBootBar will also state begin to indicate the reboot or cycle has begun 5 A new prompt tone will indicate that new commands can be entered While a reboot is in progress additional outlets can be addressed and commanded 6 The caller can hang up at any time to disconnect the call Any reboots in progress will finish their cycle time as programmed NOTE Not issuing a command for 5 seconds will ...

Page 18: ...ill be recycled again This will continue until the ping response returns or AutoPing is turned off Make sure your AutoPing frequency x Fail Count is longer than the time required to reboot your device Cycle Once Upon triggering iBootBar will cycle power one time It will not cycle again automatically until the ping response returns and is lost again With AutoPing operational the iBootBar page will ...

Page 19: ...r 5 seconds or longer will initiate a password recovery mode Once the reset button is released the user has 30 seconds to log in to the CLI using the username admin and password admin Upon accessing the CLI change the username and password for User 1 as desired iBootBar Setup and Control Utility The iBootBar Setup and Control Utility is designed to facilitate installation configuration and managem...

Page 20: ...0 2 x C14 8 x C13 I S iBB 2C10 M 2 x C14 8 x C13 I S M iBB C20 C20 8 x C13 I S iBB C20 M C20 8 x C13 I S M iBB 2C20 2 x C20 8 x C13 I S iBB 2C20 M 2 x C20 8 x C13 I S M Key Input N15 NEMA 5 15 Linecord 115VAC 15 Amps combined total switched N20 NEMA 5 20 Linecord 115VAC 20 Amps combined total switched C14 IEC320 C14 Receptacle 100 240VAC 10 Amps total at 240VAC Max C20 IEC320 C20 Receptacle 100 24...

Page 21: ...lies with Part 15 of the FCC rules Operation of this device is subject to the following conditions 1 This device may not cause harmful interference and 2 this device must accept any interference that may cause undesired operation WARNING Changes or modifications to this unit not expressly approved by the party responsible for compliance could void the user s authority to operate the equipment EMC ...

Page 22: ...e Use of the wrong countrycode violates local laws and the warranty of this product Country countrycode Argentina 07 Australia 09 Austria 253 Belgium 253 Canada 181 China 181 Cyprus 253 Czech Republic 253 Denmark 253 Finland 253 France 253 Germany 253 Greece 253 Hong Kong 153 Hungary 253 Iceland 253 Indonesia 153 Ireland 253 Italy 253 Japan 00 Korea 181 Liechtenstein 253 Luxembourg 253 Mexico 181 ...

Page 23: ...erTable 1 TE snmpManagerEntry 1 RO Integer32 snmpManagerIndex 2 RW DisplayString snmpManagerIPAddress 3 RW INTEGER Enum snmpManagerEnable 3 TB outletTable 1 TE outletEntry 1 RO Integer32 outletIndex 2 RW OCTET STRING outletName 3 RO INTEGER Enum outletStatus 4 RW INTEGER Enum outletCommand 5 RO INTEGER Enum outletAPStatus 4 BR info 1 RO Integer32 currentLC1 2 RO Integer32 currentLC2 3 RO INTEGER E...

Page 24: ...Technical Service at 201 934 5111 to receive a Return Materials Authorization RMA Number prior to sending any equipment back for repair Include all cables power supplies and proof of purchase with shipment THIS WARRANTY DOES NOT APPLY TO NORMAL WEAR OR TO DAMAGE RESULTING FROM ACCIDENT MISUSE ABUSE OR NEGLECT SELLER MAKES NO EXPRESS WARRANTIES OTHER THAN THE WARRANTY EXPRESSLY SET FORTH HEREIN EXC...