iBootBar
– Precision Version
Page 12
iBootBar_Precision_20160428e.doc
Firmware ver 1.41.32
RPS Protocol
<esc><pass><outlet><cmd><enter>
Syntax definitions:
<esc>
ASCII Escape Character (Decimal 27 Hex 1B)
<pass>
Password (no username is required)
<outlet> Outlet number, 1
– 8
Omitted for ? Status Command
<cmd>
Command to be performed
<enter>
ASCII Enter or Carriage Return Character (Decimal 13 Hex 0D)
Commands:
OFF
Turn outlet OFF
ON
Turn Outlet ON
C
Cycle Outlet
Cycle can be On-Off-On or Off-On-Off depending on
starting status
T
Set Cycle Time
Cycle time in seconds. Valid range 1-99
?
Get Status
Outlet number optional. No outlet number will respond with
status for all outlets
Examples:
<esc><pass>1ON<enter>
Turn on outlet 1
<esc><pass>3C<enter>
Cycle Outlet 3
<esc><pass>?<enter>
Status for all Outlets
<esc><pass>5?<enter>
Status for Outlet 5
Response:
<n> <status><LF><CR> (Cycle) Outlet number and Status ON or OFF. Will respond Cycle while
processing Cycle command.
For Status of all outlets:
1 On
2 OFF
3 OFF CYCLE
Indicates cycle in progress
4 ON
5 ON
6 OFF
7 ON
8 OFF