QUICK REFERENCE GUIDE
2
CONNECTIONS
EDM FBK /
SELECTION
Normally closed contact
for a force-guided relay
EDM ENABLE
RESTART
Normally closed contact
to 24 Vcc
MANUAL
RESTART
OSSD1
EDM DISABLE
RESTART SELECTION
AUTOMATIC
RESTART
FLOATING
ALIGN MODE
Cascade connection
Up to three SLIM light curtains can be connected in a cascade series. The cascade connection allows to monitor up to
three areas with only two Safety Outputs connected to Master unit. Master unit takes care of collecting safety optic
scan results from Slave units and the synchronization between them to avoid mutual interference.
Each SLIM unit can either be used as Master or Slave, only depending on cable connection
For cascaded system connection three Cascade Cables are available as accessory:
CS-H1-03-B-001
CASCADE cable 0.1 m
90
95A252950
CS-H1-03-B-005
CASCADE cable 0.5 m
490
95ASE2550
CS-H1-03-B-01
CASCADE cable 1 m
990
95ASE2560
To connect the cascade unit:
•
Fix all cascade units with proper brackets as described in par. “Mechanical Mounting” of the Instruction Man-
ual. (1)
•
Remove Terminator Caps at the end of Master and Slave 1 (if present) by loosening the two fixing screws for
both emitter and receiver. (2)
•
Fasten the cascade cables in place of removed terminator caps, ensure all cables bend radius it’s not less than
4mm (3)
•
Connect Slaves M12 male connectors to M12 Female connectors from cascade cables (4).
Receiver (RX)
Emitter (TX)
FUNCTION
CONNECTION TO
STATUS
FUNCTION
CONNECTION TO
STATUS
MODEL
DESCRIPTION
L +/- 10 (mm)
CODE