SG4 BASE
16/74
1.6 SAFETY INFORMATION
The stopping system of the machine must be electrically controlled.
This control system must be able to stop the dangerous movement of the machine within the total machine
stopping time T as per paragraph
Minimum installation distance page 12
phases.
Mounting and connection of the safety light curtain must be carried out by qualified personnel only, according
to the indications included in the special sections (refer to sections
INSTALLATION page 17
MECHANICAL
MOUNTING page 26
ELECTRICAL CONNECTIONS page 27
ALIGNMENT PROCEDURE page 33
) and in
the applicable standards.
The safety light curtain must be securely placed in a particular position so that access to the dangerous zone is
not possible without the interruption of the beams (refer section
INSTALLATION page 17
The personnel operating in the dangerous area must be well trained and must have adequate knowledge of all
the operating procedures of the safety light curtain.
Only for models SG4-xx-xxx-OO-E:
The TEST button must be located outside the protected area because the operator must check the protected
area during all Test operation.
The RESET/RESTART button must be located outside the protected area because the operator must check
the protected area during all Reset/Restart operations.
For a correct and safe use of the safety light curtains, the following points must be
observed:
Please carefully read the instructions for the correct functioning before powering the
light curtain on.