Datalogic SG-BODY Series Quick Manual Download Page 6

 

Visualization Status 

Description 

Action 

 

INTERLOCK 

Free beams, OSSDs OFF 

User can take device in normal 
operation activating restart line. 

 

INTERLOCK 

Interrupted beams, OSSDs 
OFF 

User must free beams path before 
activating restart line. 

 

NORMAL OPERATION  OSSDs ON 

 

 

SAFE 

OSSDs OFF, No code 

 

 

SAFE 

OSSDs OFF, Code 1 

 

 

SAFE 

OSSDs OFF, Code 2 

 

 

NORMAL 

OPERATION, SAFE, 

INTERLOCK 

EDM function active 

 

 

EDM function not active 

 

 

SAFE, 

INTERLOCK 

Override function ready to 
be activated 

User can activate Override function 

activating the correct sequence on 

Override lines. 

 

 

FAILURE LOCKOUT 

(recoverable) 

Failure on one or both 
OSSDs, OSSDs OFF 

User must activate RESET line. If 
ESPE does not reset user must 
contact Datalogic. 

 

 

FAILURE LOCKOUT 

(not recoverable) 

Microcontroller failure, 
OSSDs OFF 

User must turn OFF/ON ESPE. If 
the problem persists user must 
contact Datalogic. 

 

 

FAILURE LOCKOUT 

(recoverable) 

Optical failure, OSSDs OFF 

User must activate RESET line. If 
ESPE does not reset user must 
contact Datalogic. 

 

 

FAILURE LOCKOUT 

(recoverable) 

EDM failure, OSSDs OFF  

User must check EDM ENABLE line 
or dip-switches, EDM line, external 
switching device and activate 
RESET line. If ESPE does not reset 
user must contact Datalogic 
Automation Technical Support. 

 

 

FAILURE LOCKOUT 

(not recoverable) 

Override connection failure, 
OSSDs OFF 

User must check Override lines 
connection and turn OFF/ON ESPE. 
If the problem persists user must 
contact Datalogic Automation 
Technical Support. 

 

 

SAFE 

Override sequence failure, 
OSSDs OFF 

User must check Override lines 
activation sequence timings and 
repeat Override sequence. If the 
problem persists user must contact 
Datalogic. 

 

 

FAILURE LOCKOUT 

(not recoverable) 

Dip switch failure, OSSDs 
OFF 

User must check dip-switch 
configuration (see par.” DIP 
SWITCHES CONFIGURATION”) 
and turn OFF/ON ESPE. If the 
problem persists user must contact 
Datalogic Automation Technical 
Support. 

 

 

FAILURE LOCKOUT 

(recoverable) 

Internal and external lamp 
failure, OSSDs OFF 

User must check LAMP INPUT line 
and activate RESET line. If ESPE 
does not reset user must contact 
Datalogic. 

 

ESPE OFF 

Power supply failure, 
OSSDs OFF 

User must check power supply 
connection. If the problem persists 
user must contact Datalogic. 

Summary of Contents for SG-BODY Series

Page 1: ...ly read the instructions for the correct functioning before powering the light curtain Precautions to be observed for the choice and installation of the device Make sure that the protection level assured by the SG BODY device Type2 Type4 is compatible with the real danger level of the machine to be controlled according to EN 13849 1 The outputs OSSD of the ESPE must be used as machine stopping dev...

Page 2: ... M12 12 Poles 1 brown 24Vdc 2 blue 0V 3 white RESET RESTART RESTART MODE 4 green OVERRIDE1 5 pink OSSD2 6 yellow EDM 7 black MUTING ENABLE 8 grey OSSD1 9 red OVERRIDE2 10 violet LAMP INPUT 11 grey pink OVERRIDE STATUS 12 red blue EARTH M12 5 Poles 1 brown 24 Vdc 2 white MUTING2 3 blue 0V 4 black MUTING1 5 grey NOT USED M12 5 Poles 1 brown 24 Vdc 2 white TEST 3 blue 0V 4 black EARTH 5 grey NOT USED...

Page 3: ...rtain alignment can be effected only after having completed the mechanical installation and the electrical connections The following procedure has to be followed NOTE SG BODY is equipped with a system which informs the user on the alignment obtained The alignment function can be activated when powering the device by keeping the normally open RESET RESTART contact closed for at least 0 5 seconds In...

Page 4: ...n LED on the RX unit is ON and beams are not interrupted then verify that the red LED turns ON if even one single beam is interrupted SAFE condition where an object has been detected This verification shall be made with the special cylindrical Test Piece having a size suitable to the resolution of the device used refer to paragraph 3 2 6 Controls after first installation E Switch OFF and ON the de...

Page 5: ...tion Dip switches n 8 coding selection 10 min T Disabled Manual Maintained EDM on See table See table L Enabled Automatic Impulsive EDM off See table See table Dip switch n 1 coding selection Dip switch n 2 coding selection Dip switch n 3 not used Dip switch n 4 not used Dip switch n 5 not used Dip switch n 6 not used Dip switch n 7 not used Dip switch n 8 not used See table See table See table Se...

Page 6: ...RE LOCKOUT recoverable EDM failure OSSDs OFF User must check EDM ENABLE line or dip switches EDM line external switching device and activate RESET line If ESPE does not reset user must contact Datalogic Automation Technical Support FAILURE LOCKOUT not recoverable Override connection failure OSSDs OFF User must check Override lines connection and turn OFF ON ESPE If the problem persists user must c...

Page 7: ...rsists user must contact Datalogic FAILURE LOCKOUT not recoverable Optical failure User must turn OFF ON ESPE If the problem persists user must contact Datalogic FAILURE LOCKOUT not recoverable Dip switch failure User must check dip switch configuration and turn OFF ON ESPE If the problem persists user must contact Datalogic ESPE OFF Power supply failure User must check power supply connection If ...

Page 8: ...oduct In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures Datalogic S r l Via S Vitalino 13 40012 Calderara di Reno Italy Tel 39 051 3147011 Fax 39 051 3147205 www datalogic com Helpful links at www datalogic com Contact Us Terms and Conditions Support The warranty period for this product is 36 months See General Term...

Reviews: