Datalogic SG-BODY Series Quick Manual Download Page 1

 

SG-BODY MUTING SERIES 

Safety light curtains with infrared beams 

QUICK GUIDE 

 

 

This Quick Reference Guide does not replace the Instruction Manual. Download 
the Instruction Manual by reading the QR code here or at www.datalogic.com. 
Click on 

Support

 > 

Search by product

 and enter the SG 

BODY

 family name, then 

select your product from the dropdown list. Click on the 

Manuals & Technical 

Literature

 link to download your Instruction Manual. The Instruction Manual must 

be available at all times when installing and working with the product.

 

 

 

SAFETY INFORMATION 

 

The following points must be observed for a correct and safe use of the safety light curtains of the SG-
BODY series: 

 

 The stopping system of the machine must be electrically controlled. 

 This control system must be able to stop the dangerous movement of the machine within the total machine stopping 

time T as per paragraph 2.4.3 of the Instruction Manual and during all working cycle phases. 

 Mounting and connection of the safety light curtain must be carried out only by qualified personnel, according to the 

indications included in the special sections (refer to sections 3; 4; 5; 7) and in respect to the applicable Standards. 

 The safety light curtain must be securely installed so that access to the dangerous zone is not possible without 

interrupting the beams. 

 The personnel operating in the dangerous area must be well-trained and must have adequate knowledge of all the 

operating procedures of the safety light curtain. 

 The TEST, RESET/RESTART and OVERRIDE buttons must be located outside the protected area as the operator must 

check the protected area during all Test, Restart and Override operations. 

 Please carefully read the instructions for the correct functioning before powering the light curtain. 

 
Precautions to be observed for the choice and installation of the device 
 

 

Make sure that the protection level assured by the SG-BODY device (Type2/Type4) is compatible with the
real danger level of the machine to be controlled, according to EN 13849-1. 

 

 The outputs (OSSD) of the ESPE must be used as machine stopping devices and not as command devices. The 

machine must have its own START command. 

 The dimension of the smallest object to be detected must be larger than the resolution level of the device. 

 The ESPE must be installed in a room complying with the technical characteristics indicated in section 11 “Technical 

data” of the Instruction Manual. 

 Do not place the device near intense and/or flashing light sources and, in particular, close to receiving unit front surface. 

 The presence of intense electromagnetic disturbances could jeopardise device operation. This condition has to be 

carefully evaluated with the support of the Datalogic Technical service. 

 The operating distance of the device can be reduced in presence of smog, fog or airborne dust. 

 A sudden change in environment temperature, with very low minimum peaks, can generate a small condensation layer 

on the lenses and so jeopardise functioning. 

 Reflecting surfaces near the safety light curtain light beam (above, under or lateral) can cause passive reflections that 

can jeopardise functioning. 

 The safety device must be installed at a distance which is major or equal to the minimum safety distance S to ensure 

that the operator can not reach the dangerous area until the moving dangerous object has been blocked by the ESPE. 

 

 

The failure to respect the safety distance reduces or cancels ESPE the protection function. For more detailed
information about calculation of safety distance, please refer to the Instruction Manual. 

Summary of Contents for SG-BODY Series

Page 1: ...ly read the instructions for the correct functioning before powering the light curtain Precautions to be observed for the choice and installation of the device Make sure that the protection level assured by the SG BODY device Type2 Type4 is compatible with the real danger level of the machine to be controlled according to EN 13849 1 The outputs OSSD of the ESPE must be used as machine stopping dev...

Page 2: ... M12 12 Poles 1 brown 24Vdc 2 blue 0V 3 white RESET RESTART RESTART MODE 4 green OVERRIDE1 5 pink OSSD2 6 yellow EDM 7 black MUTING ENABLE 8 grey OSSD1 9 red OVERRIDE2 10 violet LAMP INPUT 11 grey pink OVERRIDE STATUS 12 red blue EARTH M12 5 Poles 1 brown 24 Vdc 2 white MUTING2 3 blue 0V 4 black MUTING1 5 grey NOT USED M12 5 Poles 1 brown 24 Vdc 2 white TEST 3 blue 0V 4 black EARTH 5 grey NOT USED...

Page 3: ...rtain alignment can be effected only after having completed the mechanical installation and the electrical connections The following procedure has to be followed NOTE SG BODY is equipped with a system which informs the user on the alignment obtained The alignment function can be activated when powering the device by keeping the normally open RESET RESTART contact closed for at least 0 5 seconds In...

Page 4: ...n LED on the RX unit is ON and beams are not interrupted then verify that the red LED turns ON if even one single beam is interrupted SAFE condition where an object has been detected This verification shall be made with the special cylindrical Test Piece having a size suitable to the resolution of the device used refer to paragraph 3 2 6 Controls after first installation E Switch OFF and ON the de...

Page 5: ...tion Dip switches n 8 coding selection 10 min T Disabled Manual Maintained EDM on See table See table L Enabled Automatic Impulsive EDM off See table See table Dip switch n 1 coding selection Dip switch n 2 coding selection Dip switch n 3 not used Dip switch n 4 not used Dip switch n 5 not used Dip switch n 6 not used Dip switch n 7 not used Dip switch n 8 not used See table See table See table Se...

Page 6: ...RE LOCKOUT recoverable EDM failure OSSDs OFF User must check EDM ENABLE line or dip switches EDM line external switching device and activate RESET line If ESPE does not reset user must contact Datalogic Automation Technical Support FAILURE LOCKOUT not recoverable Override connection failure OSSDs OFF User must check Override lines connection and turn OFF ON ESPE If the problem persists user must c...

Page 7: ...rsists user must contact Datalogic FAILURE LOCKOUT not recoverable Optical failure User must turn OFF ON ESPE If the problem persists user must contact Datalogic FAILURE LOCKOUT not recoverable Dip switch failure User must check dip switch configuration and turn OFF ON ESPE If the problem persists user must contact Datalogic ESPE OFF Power supply failure User must check power supply connection If ...

Page 8: ...oduct In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures Datalogic S r l Via S Vitalino 13 40012 Calderara di Reno Italy Tel 39 051 3147011 Fax 39 051 3147205 www datalogic com Helpful links at www datalogic com Contact Us Terms and Conditions Support The warranty period for this product is 36 months See General Term...