background image

 

 

 

 

 
 
 

 

 

 

 
 

 

L1-L2-L3 :

 Phase voltages inputs 

N :

 Neutral voltage input 

1 :

 Relay output (NC)  

2 :

 Relay output (COM) 

3 :

 Relay output (NO) 

 
 
 
 
 
 
 
 

 

ON:

   Supply LED (green) 

OUT:

 Relay output LED (yellow) 

SEQ:

 Phase sequence failure led (red) 

ASM: 

Voltage unbalance warning LED (red) 

  

SEQ  ASM  ON  OUT  DESCRIPTION 

 

 

ON 

ON 

Voltages OK 

ON 

 

ON 

 

Phase sequence trip 

 

ON 

ON 

ON 

Unbalance warning 

 

ON 

ON 

 

Unbalance trip 
Phase failure 
Overvoltage 

 
 
 

 

Nominal Supply Voltage: 

230V-AC (L-N) 

Supply Voltage Range: 

150-300 V-AC (L-N) 

Supply type:

 Capacitive, 3 phase 

Frequency Range: 

47-63Hz  

Power Consumption:

 30VA / 2W  (max) 

Measurement method:

 True RMS, line to neutral 

Asymmetry Adjustment Accuracy:

 1 % 

Repetition Accuracy:

 0.5 % 

Asymmetry Adjustment Range:

 5 

– 15%  

Over-Voltage Trip:

 240-300 V-AC (L-N)  

Under-Voltage Trip:

 150-210V-AC (L-N) 

Trip Delay Setup: 

0.5 

– 20 sec. adjustable

  

Reset Delay Setup: 

0.5 

– 20 sec. adjustable 

Relay Output:

 6A @ 277V-AC, 1800VA, 300W 

Terminal wire range

:  max 2.5mm² (12AWG)  

Screw-on Force:

 0.4 Nm (3.6 lb.in) 

Operating temp.:

 -30

C (-22

F) to 70 

C (158

F). 

Storage temp.:

    -40

C (-40

F) to 80 

C (176

F). 

Maximum humidity:

 95% non-condensing. 

Dimensions:

 36,0x90,6x58,4mm (WxHxD) 

Weight:

 100 gr(approx.) 

Installation:

 DIN Rail mounted.  

Case Material:

 High Temp. ABS/PC (UL94-V0) 

IP Protection:

 IP30 

Conformity (EU directives) 

 

-2006/95/EC (low voltage)

 

 

-2004/108/EC (EMC) 

Norms of reference: 

 

EN 61010  (safety requirements) 

             EN 60255-6 
             EN 61326  (EMC requirements) 

 

 

      

            

 

LED INDICATORS 

 

DIMENSIONS 

 

TECHNICAL SPECIFICATIONS 

 

INPUTS AND OUTPUTS 

 

INSTALLATION DIAGRAM 

 