In order to enable the 
configuration menu, 
hold both MENU buttons pressed 
for 3 seconds. 

 

 

 
When the configuration mode is entered, the 
password entry screen will be displayed. 

A  4  digit  password  must  be  entered  using 
buttons.  The  factory  default  password  is 

“9876”

.  Each  digit  is  adjusted  with 

MENU

 

buttons  and  the  next  digit  is  selected  with 

SET

 button.

 

    

 

In order to exit the configuration 
menu, hold both MENU buttons 
pressed for 3 seconds. 
If no button is pressed, the unit 
will automatically close the 
configuration menu after 30 
seconds. 

 
When  the  configuration  mode  is  entered,  a 
list  of  available  configuration  topics  will  be 
displayed as in the below screen. 
 

 

 
Navigation  on  the  list    is  made  with 

MENU

 

buttons.  Selected  configuration  topic  is 
shown  in  reverse  video  (black  on  white).  In 
order  to  enter  inside  a  configuration  topic, 
please press 

SET

 button. 

 
 
 
 
 

 

 
Select 

LCD 

CONTRAST

” 

on 

CONFIGURATION  MENU

”.  Change  the 

contrast  value  with 

MENU

  buttons  until  best 

visibility  is  obtained  and  then  press 

SET

  to 

save  new  LCD  contrast  value  and  return 
back to “

CONFIGURATION MENU

”. 

 

 

 
Select “

LANGUAGE

” on “

CONFIGURATION 

MENU

”. Select language with 

MENU

 buttons 

then press 

SET

 to save the new language 

and return to “

CONFIGURATION MENU

”. 

 

 

 

For the correct current measurement, the 
current transformer ratio has to be set 
properly.  

The secondary of the current transformer is 
always supposed to be 5 Amps. Only the 
primary value is set. 

Select “

CRNT TRF RATIO

” on 

CONFIGURATION MENU

”.  

Then  adjust  the  current  transformer 

ratio  with 

MENU

  buttons  until  required  value 

then  press 

SET

  button  to  save  the  new 

current  transformer  ratio  and  return  to 

CONFIGURATION MENU

”. 

 

 

 

If a voltage transformer is used, then its ratio 
needs to be set to the unit.  

The voltage transformer ratio is defined as 
primary voltage / secondary voltage. The 
secondary is always supposed 1.0. Thus only 
the primary is programmed. 

Select “

VOLT TRF RATIO

” on 

CONFIGURATION MENU

”.  

Adjust the voltage transformer ratio with 

MENU

 buttons until required value then press 

SET

 button to save new voltage transformer 

ratio and return to “

CONFIGURATION 

MENU

”. 

VOLTAGE TRANSFORMER RATIO 

 

CURRENT TRANSFORMER RATIO 

 

LANGUAGE SELECTION 

 

ADJUSTING THE LCD CONTRAST 

 

DEVICE CONFIGURATION 

 

Summary of Contents for DKM-409

Page 1: ... specified in the user manual Do not try to clean the device with solvent or the like Only clean with a dry cloth Verify correct terminal connections before applying power Only for front panel mounting Before installation Read the user manual carefully determine the correct connection diagram Remove all connectors and mounting brackets from the unit then pass the unit through the mounting opening ...

Page 2: ...WG15 cable The current transformer cable length should not exceed 1 5 meters If longer cable is used increase the cable section proportionally Current transformers must have 5A output For the RS 485 connection use appropriate shielded twisted wire cable Communication quality will depend highly on the cable used Do not install the unit close to high electromagnetic noise emitting devices like conta...

Page 3: ...CONNECTION DIAGRAM FOR 230 400V NETWORK ...

Page 4: ...R FOR 3 SEC Clears visual warning condition if any If no warning condition enters configuration mode The unit offers the possibility of automatically scanning of all display screens In order to enable auto scroll function hold the SET button pressed for 3 seconds In order to disable auto scroll function hold the SET button pressed for 3 seconds When the auto scroll is enabled the unit will switch ...

Page 5: ...ave new LCD contrast value and return back to CONFIGURATION MENU Select LANGUAGE on CONFIGURATION MENU Select language with MENU buttons then press SET to save the new language and return to CONFIGURATION MENU For the correct current measurement the current transformer ratio has to be set properly The secondary of the current transformer is always supposed to be 5 Amps Only the primary value is se...

Page 6: ...n 1000V AC 1 minute Serial Port Signal level RS 485 Communication Modbus RTU Data Rate 9600 b no parity 1 bit stop Isolation 500V AC 1minute Serial port cable 2 wires twisted shielded cable Max 60pF meter Operating Temperature 20 C to 70 C 4 to 158 F Maximum humidity 95 non condensing Degree of Protection IP 54 Front Panel IP 30 Back panel Enclosure Non flammable ROHS compliant ABS PC UL94 V0 Inst...