DKM-250 User Manual V-2.0
29
If any of relay functions (explained in chapter 4.17) is set to 14 (kWh, Ah or hour-run pulse),
then below parameters will determine the pulse charateristics.
This parameter defines the counter increment step to provide 1 pulse.
The factory set value is 1.000 kWh or Ah or hour.
Adjustement range is 0.001 to 10.000
This parameter defines the active pulse duration in seconds.
The factory set value is 0.20 second (200 ms).
Adjustment range is 0.10 to 9.99 seconds.
WARNING:
Excessive pulse duration may cause a missing pulse.
This parameter defines the minimum duration between 2 pulses.
The factory set value is 0.20 second (200 ms).
Adjustment range is 0.10 to 9.99 seconds.
WARNING:
Excessive duration may cause a missing pulse.
This parameter determines the counter providing pulses.
0:
Positive direction kWh counter
1:
Negative direction kWh counter
2:
Positive direction Ah counter
3:
Negative direction Ah counter
4:
Total hours-run counter
The factory set value is 0.
Adjustment range is 0 to 4 seconds.
4.20 OUTPUT PULSE (kWh, Ah, hour) SETUP