DKM-250 User Manual V-2.0
28
Digital input functions are selected from below list:
Value Function when signal is active
Function when signal is passive
0
-
-
1
kWh and Ah counters operate
kWh and Ah counters are stopped
2
When signal is activated, kWh and Ah
counters are reset, then they start
counting
kWh and Ah counters are stopped
3
kWh, Ah and hours-run counters
operate
kWh, Ah and hours-run counters are
stopped
4
When signal is activated, kWh, Ah and
hours-run counters are reset, then
they start counting
kWh, Ah and hours-run counters are
stopped
5
hours-run counter operates
hours-run counter is stopped
6
When signal is activated, the hours-
run counter is reset, then it starts
counting
hours-run counter is stopped
7
When signal is activated, kWh and Ah
counters are reset
-
8
When signal is activated, The hours-
run counter is reset
-
9
When signal is activated, kWh and Ah
counters are reset
-
10
Alarms are reset
-
11
When signal is active, displays turn off Displays operate normally
This parameter selects when the input function is activated for the
digital input_1.
0:
active when signal present
1:
active when signal is absent
The signal is applied to digital inputs with the polarity shown in the
installation diagram.
The factory set value is 0.
This parameter selects when the input function is activated for the
digital input_2.
0:
active when signal present
1:
active when signal is absent
The signal is applied to digital inputs with the polarity shown in the
installation diagram.
The factory set value is 0.