Although the unit is protected against electromagnetic disturbance, excessive disturbance
can affect the operation and measurement precision
ALWAYS remove plug connectors when inserting wires with a screwdriver.
Fuses must be connected in series with the power supply, in close proximity of
the unit.
Fuses must be of fast type (FF) with a maximum rating of 6A.
Use cables of appropriate temperature range.
Use adequate cable section, at least 0.75mm
2
(AWG18).
1.3 ELECTRICAL INSTALLATION
Do not install the unit close to high electromagnetic noise
emitting devices like contactors, high current busbars,
switchmode power supplies and the like.
Be sure that the relay outputs are not over-loaded.
Use auxiliary contactors if necessary.