DKM-0208 

ALARM ANNUNCIATOR 

 
 
 
 
 

    

 

 

 
The DKM-0208 is an 8 channel, 96x96mm alarm 
annunciator designed to be used in energy and 
automation systems. 
Optically isolated digital inputs are equipped with 
noise cancelling filters and are capable of 
operating smoothly in high electrical noise 
environments. The detection delay of inputs are 
adjustable between 2 and 500ms. 
The module features 3 relay outputs rated at 
5Amp. Relays provide Horn, Bell and Internal 
Failure functions. An additional buzzer is provided 
inside the unit for audible alarms. 
The unit features ultra-bright, bicolor (red-green) 
led indicators. Alarms may be assigned to 
different priority levels in order to reduce 
confusion. 
Using front panel pushbuttons, alarms may be  
acknowledged and reset, the unit tested. 
The configuration of the module is performed with 
jumpers placed on the back panel. Additional 
programming may be performed from the front 
panel or through programming software. 
The isolated RS-485 MODBUS RTU 
communication port is free from ground potential 
differences and allows safe transfer of measured 
parameters to automation and monitoring 
systems. 
It is possible to monitor the module and keep 
records with Datakom   software. 
The supply input is isolated from other terminals. 
The module has two supply versions  being 19-
150V-DC or 85-305V-AC (88-400V-DC). 
 

  

 

   

 

 

When the unit detects a fault signal from an input, 
the related alarm led becomes active.  
 

FAST FLASH:

 At the first detection of the fault. 

SLOW FLASH:

 Activated when the ACK(alarm 

acknowledge) pushbutton is pressed and if the 
fault is still active. 

STEADY ON:

 Activated if the fault signal 

disappears at SLOW FLASH condition. 

LED OFF:

 The alarm led turns off when RESET 

pushbutton is pressed and fault signal is not 
present.  
 
When a fault signal is detected, the internal 
buzzer turns on with a period of 1 second. If ACK 
pushbutton is pressed, the buzzer turns off. If 
ACK is not pressed within 1 minute, then it 
switches to slow sound mode (beeps once every 
10 seconds.) 

HORN RELAY:

 

If any “red” alarm led turns on, 

then the horn relay will also turn on. The relay 
turns off when ACK pushbutton is pressed. 

BELL RELAY:

 

If any “green” alarm led turns on, 

then the bell relay will turn on. The relay turns off 
when ACK pushbutton is pressed. 

WATCHDOG RELAY:

 At startup the relay turns 

on. If the board fails, then it turns off. 

HORN/BELL LED:

 If the HORN relay turns on, 

the “red” led turns on. If the HORN relay is not on 
and if 

the BELL relay is on, then the “green” led 

turns on. If both relays are off then the led is off. 

SAFE/FAIL LED:

 If an internal fault condition is 

detected at self-test, then this led will turn on 
“red”, else it turns on “green”. 

DESCRIPTION

 

FEATURES

 

Summary of Contents for DKM-0208

Page 1: ...input is isolated from other terminals The module has two supply versions being 19 150V DC or 85 305V AC 88 400V DC When the unit detects a fault signal from an input the related alarm led becomes ac...

Page 2: ...of fast type FF with a maximum rating of 6A Disconnect all power before working on equipment When the unit is connected to the network do not touch terminals Short circuit terminals of unused current...

Page 3: ...INSTALATION 1 3 ELECTRICAL INSTALLATION 2 PUSHBUTTON FUNCTIONS 3 LED FUNCTIONS 4 SETTINGS 4 1 JUMPER SETTINGS 4 2 SIGNAL LED RED GREEN SETTINGS 4 3 BUZZER SETTINGS 5 MODBUS COMMUNICATION 5 1 INTRODUC...

Page 4: ...cal connections with plugs removed from sockets then place plugs to their sockets Otherwise the sockets may get damaged Be sure that the relay outputs are not over loaded Use auxiliary contactors if n...

Page 5: ...DKM 0208 User Manual V 1 0 26 10 2015 5 Panel Cutout Required Panel Depth 1 1 FRONT and BACK PANELS 1 2 MECHANICAL INSTALLATION...

Page 6: ...ries with the power supply in close proximity of the unit Fuses must be of fast type FF with a maximum rating of 6A Use cables of appropriate temperature range Use adequate cable section at least 0 75...

Page 7: ...s the buzzer function can be disabled enabled By pressing the pushbutton again the module exits from the test This button is also used in settings menu If the pushbutton is pressed all leds turn on wi...

Page 8: ...RN relay turns on the red led turns on If the HORN relay is not on and if the BELL relay is on then the green led turns on If both relays are off then the led is off FAIL SAFE LED If an internal fault...

Page 9: ...long for 3 seconds first led flashes with the adjusted color By pressing RESET pushbutton signal leds can be selected from up to down by pressing HORN pushbutton signal leds can be selected from left...

Page 10: ...her details of Modbus Protocol Modicon Modbus Protocol Reference Guide can be rewieved The guide can be downloaded from www modbus org docs PI_MBUS_300 pdf Supported Function Function 3 Read multiple...

Page 11: ...signed word 1 20481 Baudrate Modbus Baudrate Value 16 BIT R O unsigned word 1 20482 Node Adress Modbus Node Adress Value 16 BIT R O unsigned word 1 20483 Jumper Value Jumper Value 16 BIT R O unsigned...

Page 12: ...er 80dB Relay outputs 3 x 5A 250V AC Serial Port Signal Type RS 485 Protocol Modbus RTU Data Rate 9600 19200baud Isolation 1000V AC 1 minute Operating Temperature Range 20 C 70 C Storage Temperature R...

Reviews: