DKG-225 User Manual Firmware V-01
- 33 -
PGM
Parameter Definition
Unit
Fact.Set Description
P_32
Genset Contactor
Timer
sec
1
This is the period after the mains contactor has
been deactivated and before the generator
contactor has been activated.
P_33
Mains Contactor
Timer
sec
1
This is the period after the generator contactor has
been deactivated and before the mains contactor
has been activated.
P_34
Number of Starts
-
3
This is the maximum number of start attempts.
P_35
Alarm Relay Timer
sec
60
This is the period during which the ALARM relay is
active. If the period is set to 0, this will mean that
the period is unlimited.
P_36
Intermittent Alarm
Relay
-
0
0: continuous
1: intermittent (turns on and off every second)
P_37
Service Engine Hours
hour
50
The SERVICE REQUEST led indicator will turn on
after this quantity of engine hours from the last
service. If the period is set to ‘0’ no SERVICE
REQUEST will be generated depending on engine
hours.
P_38
Service Period
month
6
The SERVICE REQUEST led indicator will turn on
after this amount of time from the last service. If
the period is set to ‘0’ no SERVICE REQUEST will
be indicated depending on time.
P_39
Crank Cut Frequency
Hz
10.0
When the genset frequency reaches this limit, the
engine is supposed running and the crank output
will release.
P_40
Crank Stop with Oil
Pressure
-
0
0: no crank stop with oil pressure
1: cranking is stopped when oil presure switch is
open or the oil pressure measured is above
shutdown limit.
P_41
Crank Stop with
Charge
-
0
0: no crank stop with charge input
1: cranking is stopped when the charge alternator
voltage is established.
P_42
Charge Alternator
Shutdown
-
0
0: The charge input generates CHARGE FAIL
warning, and does not stop the engine.
1: The charge input generates CHARGE FAIL
alarm, and stops the engine.
P_43
Line-to-Line Voltages
-
0
0: Display Line to Neutral voltages as default
1: Display Line to Line voltages as default
P_44
Emergency Backup
Operation
-
0
0: In TEST mode, the load will not be transferred
to the genset even if the mains fail.
1: In TEST mode, the load will be transferred to
the genset if the mains fail.
P_45
Remote Start Enable
-
0
0: no Remote Start signal
1: SPARE input is Remote Start signal
P_46
Simulate Mains
Enable
-
0
0: no Simulate Mains signal
1: SPARE input is Simulate Mains signal
P_47
Delayed Simulate
Mains
-
0
0: The SPARE input has normal function
1: The SPARE input has delayed simulate mains
function. See chapter 12.3 for more info.
P_48
Flashing Relay Timer
Engine running timer
hours
0
Delayed Simulate Mains Operation:
max
genset running time after Simulate Mains signal
disappears.
Dual Genset Systems:
flashing relay ON state
duration timer.