DKG-109 User Manual V-27
(23.08.2013)
- 32 -
Program Group: Electrical Parameters
Parameter Definition,
(Password Level)
Unit Factory
Set
Description
(2)
2
nd
Overcurrent Limit
A
0
When secondary volt/freq limits are active:
If the current goes above this limit, during the period
defined in
Overload Timeout
then a
Overcurrent Load
Dump
alarm will be generated.
If this parameter is 0 then Overcurrent check is disabled.
(1)
2
nd
Mains Voltage Low
Limit
V
84
When secondary volt/freq limits are active:
If one of the mains phases goes under this limit, it
means that the mains are off and it starts the transfer
to the genset in
AUTO
mode.
(1)
2
nd
Mains Voltage High
Limit
V
136
When secondary volt/freq limits are active:
If one of the mains phases goes over this limit, it
means that the mains are off and it starts the transfer
to the genset in
AUTO
mode.
(2)
2
nd
Mains Frequency
Low Limit
Hz
55
When secondary volt/freq limits are active:
If the mains frequency goes under this limit, it means
that the mains are off and it starts the transfer to the
genset in
AUTO
mode.
(2)
2
nd
Mains Frequency
High Limit
Hz
65
When secondary volt/freq limits are active:
If the mains frequency goes above this limit, it means
that the mains are off and it starts the transfer to the
genset in
AUTO
mode.
(2)
2
nd
Genset Low Voltage
Shutdown Limit
V
90
When secondary volt/freq limits are active:
If one of the generator phase voltages goes under this
limit when feeding the load, this will generate a
GENSET
LOW VOLTAGE
shutdown alarm
and the engine will
stop.
(2)
2
nd
Genset Low Voltage
Warning Limit
V
94
When secondary volt/freq limits are active:
If one of the generator phase voltages goes under this
limit when feeding the load, this will generate a
GENSET
LOW VOLTAGE
warning.
(2)
2
nd
Genset High Voltage
Warning Limit
V
130
When secondary volt/freq limits are active:
If one of the generator phase voltages goes above this
limit when feeding the load, this will generate a
GENSET
HIGH VOLTAGE
warning.
(2)
2
nd
Genset High Voltage
Shutdown Limit
V
136
When secondary volt/freq limits are active:
If one of the generator phase voltages goes over this
limit when feeding the load, this will generate a
GENSET
HIGH VOLTAGE
alarm and the engine will stop.