DFC-0108 is a high technology controller 
allowing the power factor of the installation to 
be stabilized to the requested value by 
switching capacitor banks through contactors. 
The unit allows also the visualization of 
various AC parameters like a network 
analyzer. 

The unit makes harmonic analysis up to the 
31th component. The THD values of all 
voltages and currents are available. 

Stepping algorithms are selectable between 
various types. Thanks to the automatic setup 
function, the commissioning and programming 
are made easy. 

 

* Electrical equipment should be installed only 
by qualified specialist. No responsibility is 
assured by the manufacturer or any of its 
subsidiaries for any consequences resulting 
from the non-compliance to these instructions. 

* Check the unit for cracks and damages due 
to transportation. Do not install damaged 
equipment. 

* Do not open the unit. There is no 
serviceable parts inside. 

* Fuses of fast type (FF) with a maximum 
rating of 6A must be connected to phase 
voltage inputs, in close proximity of the unit. 

* Disconnect all power before working on 
equipment. 

* When the unit is connected to the network 
do not touch terminals. 

* Short circuit terminals of unused current 
transformers. 

* Any electrical parameter applied to the 
device must be in the range specified in the 
user manual. 

* Do not try to clean the device with solvent or 
the like. Only clean with a dry cloth. 

* Verify correct terminal connections before 
applying power. 

* Only for front panel mounting. 

 

 

 

 

Before installation: 

 Read the user manual carefully, determine 

the correct connection diagram. 

 Remove all connectors and mounting 

brackets from the unit, then pass the unit 
through the mounting opening. 

 Put mounting brackets and tighten. Do not 

tighten too much, this can brake the 
enclosure.  

 Make electrical connections with plugs 

removed from sockets, then place plugs to 
their sockets.

 

 Be sure that relay outputs are not 

overloaded. If necessary use extra 
contactors.

 

Below conditions may damage the device: 

 Incorrect connections. 

 Incorrect power supply voltage. 

 Voltage at measuring terminals beyond 

specified range. 

 Current at measuring terminals beyond 

specified range. 

 Overload or short circuit at relay output 

 

Below conditions may cause abnormal 
operation: 

 Power supply voltage below minimum 

acceptable level. 

 Power supply frequency out of specified 

limits 

 Current transformers not matching related 

phases. 

 Current transformer polarity incorrect. 

 Inadequate on-delay setting 

 Inadequate off-delay setting 

INSTALLATION

 

Detailed user manual of this product 

may be downloaded at: 

www.datakom.com.tr 

 

 

Current Transformers must be 
used for current measurement.  

No direct connection allowed

 

 

 

SAFETY NOTICE  
Failure to follow below 
instructions will result in 
death or serious injury

 

 

DFC-0108 POWER FACTOR CONTROLLER 

 8 BANKS, HARMONIC DISTORTION 

DISPLAY

 

 

Summary of Contents for DFC-0108

Page 1: ...t try to clean the device with solvent or the like Only clean with a dry cloth Verify correct terminal connections before applying power Only for front panel mounting Before installation Read the user manual carefully determine the correct connection diagram Remove all connectors and mounting brackets from the unit then pass the unit through the mounting opening Put mounting brackets and tighten D...

Page 2: ... 2 5 5 A AC Accuracy Voltage 0 5 1digit Current 0 5 1 digit Frequency 0 5 1 digit Power kW kVAr 1 0 2digit Power factor 0 5 1digit Measurement Range CT range 5 5A to 5000 5A VT range 0 1 1 to 200 0 1 kW range 0 1 kW to 6 5 MW Power Consumption 4 W Voltage burden 0 1VA per phase Current burden 1VA per phase Steps 8 Relay Outputs 5A 250V AC Operating Temperature 20 C to 80 C 4 to 176 F Maximum humid...

Page 3: ...d value programming mode Switch to lower display or next parameter or decrease related value programming mode HELD PRESSED DURING 5 SEC Switches between AUTO and MANUAL modes In MANUAL mode the stepping is disabled From the MANUAL mode TEST mode can be selected in order to test each step manually HELD PRESSED DURING 5 SEC IN MANUAL MODE Switches between MANUAL and TEST modes In TEST mode all steps...

Page 4: ...ng the MENU pushbutton will select the next step and the related step led will flash Using pushbuttons the step may be activated or deactivated Using the MENU pushbutton all steps may be scrolled manually In TEST mode if no button is pressed during 1 minute the unit will automatically return back to MANUAL mode Holding the pushbutton pressed for 5 seconds switches between TEST and MANUAL modes TES...

Page 5: ...atings In such cases auto setup should be repeated and capacitor ratings should be checked corrected through PROGRAMMING menu For a successful auto setup current transformers must be connected to correct CT inputs The connection polarity is not important Otherwise the unit will give ALARM_03 and will not perform automatic setup For a successful auto setup STEP_1 capacitors must be 3 phased Otherwi...

Page 6: ...and the unit will ask the power meter type Press again the MENU button The display will show the power meter type Adjust required power meter type with arrow buttons 0 mechanical power meter 1 digital power meter Press again the MENU button The display will show LErn and the unit will ask to enter the quick commissioning mode Press again the MENU button The display will show 0 Set the parameter to...

Page 7: ...EQUENCY Occurs if the frequency is below F Lo limit during F dU period AL 08 EXCESS kW Occurs if the total active power is above A Hi limit during A dU period AL 09 LOW kW Occurs if the total active power is below A Lo limit during A dU period AL 10 EXCESS INDUCTIVE kVAr Occurs if the total reactive power is inductive and above rInd limit during r dU period AL 11 EXCESS CAPACITIVE kVAr Occurs if t...

Page 8: ...L1 L2 L3 N 6A 6A 6A L1 L2 L3 GN 6A GENERATOR PHASE CONNECTION DIAGRAM ...

Reviews: