8) On
Modem
box select
Internal
or
GSM Datakom
following your modem
configuration
9)
Baud rate
selection does not apply to internal modem. Select 57400 baud for
external modem.
10)Select
Communication>IP Settings
tab. This page contains IP related communication
parameters.
11) User IP Mask
parameters are used for restricting the external access to the embedded
web server. Leave these fields unchanged as above for unrestricted access. Please
consult
Datakom
for more details.
12) Rainbow Server Adresses
are used for
RainbowScada
remote monitoring program. If
RainbowScada program is installed, the IP address (or domain name) of the central
monitoring PC should be entered. If only one center is used, enter both addresses the
same. Set the
Rainbow Server Port
to the same value set in the
RainbowScada
program.