Each DSCP62 Thermocouple Converter provides a single channel of thermocouple 
input which is amplified, linearized and converted to a high-level current or voltage 
output. Thermocouple type, measurement range, filter, output type and range, 
and fault indication may be configured by dip-switch. An auxiliary relay output 
is provided to generate an alarm or act as a thermostat. Power can be applied 
directly to the converter’s terminals or through a DIN rail mounted bus connector 
accessory, eliminating the need to wire power to each individual converter.

Specifications

 

Typical at T

A

=+25°C and +24VDC power

Installation rules

This module is designed for assembly on a DIN 46277 rail. Assembly in a 
vertical position is recommended to increase the module’s ventilation. Be 
sure that no raceways or other objects that compromise aeration are posi-
tioned in the vicinity, and do not position the module above equipment that 
generates heat. We recommend positioning the module in the lower part of 
the control panel or container compartment. We also recommend rail-type 
assembly using the Power Bus connector, which eliminates the need to con-
nect the power supply to each module.

Range and precision of the input

Thermocouple

Range

Mean error

Resolution

J

–210 to 1200°C

0.025% + 0.29°C

0.12°C

K

–200 to 1372°C

0.025% + 0.4°C

0.17°C

E

–200 to 1000°C

0.025% + 0.2°C

0.92°C

N

–200 to 1300°C

0.025% + 0.42°C

0.19°C

S

–50 to 1768°C

0.025% + 1.34°C

0.66°C

R

–50 to 1768°C

0.025% + 1.19°C

0.59°C

B

  250 to 1820°C *

0.025% + 1.87°C

0.9°C

T

–200 to 400°C

0.025% + 0.31°C

0.13°C

* Up to 250°C, the output is considered equivalent to 0°C.

Dataforth Corporation

 

3331 E. Hemisphere Loop • Tucson, AZ  85706  USA • Toll Free: 800-444-7644 • Tel:  520-741-1404 • Fax: 520-741-0762 • Email: [email protected] • 

www.dataforth.com

SD1145   02/11 

 

©

2011 Dataforth Corporation, All Rights Reserved  ISO9001:2008 Registered QMS 

 

 

 

 

 

 

      1

Module

DSCP62

Input (selectable)

   Thermocouple Type 

   EN 60584-1

J, K, E, N, S, R, B, T

Measurement range: Depends on 

thermocouple type and dip-switch setting

Span: 100°C (min)

  Input Impedance

10MΩ

Accuracy 

±0.1% (max)

Cold Junction Error

1.5°C (max)

Thermal Drift

<120ppm/°K

A/D Conversion

14-bit

Processing

Floating point 32-bit

Response Time, 90% Span 

(selectable)

<25ms (without filter), <55ms (with filter)

CMRR

>135dB, referred to power supply side

Isolation

1500Vrms (1 minute), 3-Way

Dip-Switch Configuration

Sets input and output ranges, sensor type, 

filter and faults

Status Indicators (LED)

Internal fault, configuration error,  

connection fault

Output (selectable)
   Current

0 to 20, 4 to 20, 20 to 0 or 20 to 4mA   

Load resistance: 500Ω (max)

   Current Output Protection

25mA (max)

   Fault Output 

102.5% or 105% of full-scale value in  

case of over-range

   Voltage

0 to 5, 1 to 5, 0 to 10 or 10 to 0VDC  

Load resistance: 2kΩ (min)

   Auxiliary Relay Output

Rated 60mA (max) at 24VAC

Power Supply

19.2 to 30VDC

Power Consumption

<600mW (24mA at 24VDC)

Hot Swapping

Yes

Environmental
   Operating Temp. Range

–20°C to +65°C

   Storage Temp. Range

–40°C to +85°C

   Relative Humidity

0 to 90%, Noncondensing

   IP Protection

IP20

Emissions

EN61000-6-4

Immunity

EN61000-6-2

Mechanical Dimensions (w x h x d)

0.24" x 3.67" x 4.04"   

(6.2mm x 93.1mm x 102.5mm)

Housing

Terminal housing for mounting on  

35mm DIN 46277

Connections

Spring cage clamp

Weight

1.6 ounces  (46g) 

Auxiliary Output

The auxiliary output is designed to drive an indicator, a relay of greater 
power, or the input of a supervisory control system. Through this output the 
DSCP62 module can generate an alarm or be utilized like a thermostat. The 
normal state of the output depends on the configuration for the fault of the 
primary output.

Setting the threshold

The regulation of the threshold is performed through a button located under 
the front cover of the module and accessible through the hole using a small 
screwdriver. 

•  Press and release the button. The primary output will start to represent 

the value of threshold and the red LED will flash slowly.

•  If the button is not pressed again within 5 seconds, the system will 

return to standard functioning.

•  Each time the button is pressed there is an increase or decrease of the 

primary output of approximately 0.2%; the direction of the variation 
depends on the configuration of the output. 

•  If the button is not released but continues to be pressed, a continuous 

3% increase starts after 2 seconds.

•  When the maximum/minimum value of the chosen scale is reached, the 

cycle starts again.

•  During regulation of the threshold, the auxiliary output follows standard 

functioning, opening and closing as previously set.

•  After 5 seconds of no button pressing, the set value is memorized and 

the module continues with standard functioning.

SW2.7

Regulation type

Fault

Standard state

Set threshold

OFF

Furnace *

Upscale

Closed (LED ON)

Decrease

ON

Refrigerator *

Downscale

Open (LED OFF)

Increase

* In case of choice of direct output: 0(4) to 20mA, 0(1) to 5(10)V