SUMMARY OF AVR CONTROLS

CONTROL

FUNCTION

DIRECTION

VOLTS

STABILITY

STAB  SWITCH

UFRO

DROOP

VTRIM

EXC TRIP

TO ADJUST GENERATOR OUTPUT VOLTAGE 

TO PREVENT VOLTAGE HUNTING 

TO OPTIMISE TRANSIENT PERFORMANCE 

TO SET THE UFRO KNEE POINT 

TO SET THE GENERATOR DROOP TO 5% AT OPF 

TO OPTIMISE ANALOGUE INPUT SENSITIVITY 

TO SET OVER EXCITATION  TRIP CUT OFF LEVEL

CLOCKWISE INCREASES OUTPUT VOLTAGE 

CLOCKWISE INCREASE THE DAMPING EFFECT 

SEE TABLE ABOVE

CLOCKWISE REDUCES THE KNEE POINT FREQUENCY 

CLOCKWISE INCREASES THE DROOP 

CLOCKWISE INCREASES THE GAIN OR SENSITIVITY 

CLOCKWISE INCREASES THE CUT OFF LEVEL

The main functions of the AVR are:

Potential  Divider  and  Rectifier  takes  a  proportion  of  the 
generator  output  voltage  and  attenuates  it.  The  potential 
divider  is  adjustable  by  the  AVR  Volts  potentiometer  and 
external  hand  trim mer  (when  fitted).  The  output  from  the 
droop  CT  is  also  added  to  this  signal.  A  rectifier  converts 

the a.c.  input signal  into d.c. for further processing.

The  DC  Mixer adds  the Analogue  input  signal  the  Sensing 
signal.

The  Am plifier  (Amp)  compares  the  sensing  voltage  to  the 

Reference  Voltage  and  amplifies  the  difference  (error)  to 

provide  a  controlling  signal  for  the  power  devices.  The 
Ramp  Generator  and  Level  Detector  and  Driver  infinitely 
control  the conduction period  of the  Power Control  Devices 
and  hence  provides the  excitation system  with the required 
power  to  maintain  the  generator  voltage  within  specified 
limits.

The  Stability  Circuit  provides  adjustable  negative  ac 
feedback  to  ensure  good  steady  state  and  transient 
performance of the control  system.

The  Low  Hz  Detector  measures  the  period  of  each 
electrical  cycle  and  causes  the  reference  voltage  to  be 
reduced  approximately  linearly  with  speed  below  a 
presettable  threshold.  A  Light  Emitting  Diode  gives 
indication of underspeed running.

T h e   S yn chronising  circu it  is  used  to  keep  the  Ram p 

G enerator  and  L ow  Hz  D e te cto r locked to the generator 

waveform  period.

T he  Low   Pass  Filter  prevents  distorted  w aveform s 
a ffe ctin g   the  ope ration  o f  th e  A V R   c o n tro l  circuit.

T h e   S h ort  C ircuit  D e te cto r  senses  the  presence  o f  a 
short  circuit  on  the  gen era tor  o u tp u t  a n d   fo rc e s   the 
P o w er  C ontrol  Devices  into  full, conduction.  This  only 
occurs  w hen  the  A V R   is  pow ered  fro m   an  auxiliary 
winding.

Power  Control  Devices  va ry  th e   a m o u n t  o f e xciter  field 

curre nt  in  response  to  the  e rro r signal  produced  by  the 
Amplifier.

Suppression  co m p o n e n ts   a re   in clu d e d   to   pre ve n t  sub 

cycle  voltage  spikes  dam aging  the  A V R   com pone nts 

and  also  to  reduce  the  am ount  o f  c o n d u c te d   n o ise   on 
the generator terminals.

The  Over Excitation  Detector c o n tin u o u s ly   m o n ito rs   the 

e xciter  field  voltage  and  provides  signals,  to  collapse 

the  output  voltage  if  an  over  e x c ita tio n   c o n d itio n  
persists for the specified time period.

The  Power  Supply  provides  the  required  voltages  for 
the AVR circuitry.

ADJUSTMENT OF AVR CONTROLS

V O LTA G E ADJUSTMENT

T h e   g e n e ra to r o u tp u t v o lta g e   is  s e t a t th e  fa cto ry,  but 

ca n   be  a lte re d   by  ca re fu l  a d ju s tm e n t o f th e  V O L T S  
c o n tro l  o n  th e  A V R   b oa rd,  o r by th e   e x te rn a l  ha n d  

trim m e r  if fitted.  If m a jo r a d ju s tm e n t  is  n e ce ssa ry  o r  

yo u   lo se   sta b ility,  fo llo w  th e   V O LTA G E  SETUP 

PROCEDURE’.

Terminals  1  and 2 on  the AVR will  be fitted with a  shorting 

link if no hand trimmer is required.  Terminals  La and  Lb are 
linked only for special  low voltage applications.

W ARNING !  Do  not  increase  the  voltage  above  the  rated 
generator  voltage. 

If  in  doubt,  refer  to  the  rating  plate 

m ounted on the generator case.

W ARNING ! 

Do  not  ground  any  of  the  hand  trimmer 

terminals  as  these  could  be  above  earth  potential.  Failure 
to observe this could cause equipment damage.

W ARNING!

If  a  replacement  AVR  has  been  fitted  or  re-setting  of  the 

VOLTS  adjustment  is  required,  turn  the  VOLTS  control 
fully anti-clockwise  before running generator.

VO LTA G E SETUP PROCEDURE

For m ajor adjustments and replacing the AVR.

Read  and  und erstand th is  p ro ce d u re   before 

a tte m p tin g  to  fo llo w   it.

1.  B e fo re   ru n n in g   g e n e ra to r, tu rn   the  V O L T S   co n tro l 

fully anti-clockwise.

2.  Turn  remote  volts  trim m e r  ( if  fitte d )  to   m id w a y  

position.

3. Turn STABILITY control to midway position.
4.  Connect a suitable voltmeter (0-300V ac)  across  line to

5.  S ta rt g e n era tor set,  and  ru n  o n   n o   lo a d   at  n o m in a l 

frequency e.g.  50-53Hz or 60-63Hz.

6 .  If th e   re d   L ig h t  E m ittin g   D iode  (LED)  is illum inated, 

refer to the Under Frequency Roll  O ff (UFRO)adjustment.

7.  Carefully turn VOLTS  control  clockwise until rated 

voltage  is reached.

8.  If  instability  is  present  at  rated  voltage,  refer  to 

stability 

adjustment, 

then  re-adjust 

voltage 

if 

necessary.

9.  Voltage adjustment is  now completed.