8.1.1
Alarm of temperature limit safety controller
Safety controller temperature alarm
The set temperature limit
(parameter “Al.5”) has been exceeded (Table 3 on page 30 or Table 4 on page
•
Alarm message emitted immediately
•
Audible alarm: buzzer (ongoing sound)
•
Visual
display:
LED
Upper display, changing content
Actual temperature
Alarm code
flashes
permanently lit
•
Measures
1. Check the setting of the temperature limit
(parameter “Al.5”)
(Table 3 on page 30 or Table 4 on page
The value of parameter “Al.5” should be at least by 5 °C above the value of parameter “SP”.
If necessary, change this parameter.
2. Check whether samples were inserted into the chamber that produces heat under the climate
conditions in the device.
3. Check the ambient temperature.
The ambient temperature must be below 32°C.
The unit must be protected against direct sunlight.
The installation location must be sufficiently ventilated to prevent any build-up of heat in the device.
4. If you can exclude points 1. to 3. as the source of the fault, the device might be faulty. Please
contact your local Datacolor service representative.
8.1.2
Alarm of temperature tolerance range
Main controller temperature alarm.
The set-point temperature (parameter “SP”) has been exceeded or fallen below by more than 2°C for
more than 20 minutes.
•
Audible alarm: buzzer (intermittent sound)
•
Visual
display:
LED
Upper display, changing content
Actual temperature
Alarm code
flashes
flashes
•
Measures
1. Check the ambient temperature. The ambient temperature must lie between 18 and 32°C.
2. Regarding to the displayed actual temperature, check if the set-point temperature (parameter “SP”)
has been
exceeded or fallen below.
3. Check if a prolonged door opening has caused the temperature deviation. In this case, no further
actions are required. If appropriate, mute the buzzer.