Dap4 LonWorks Interface Instructions 

Document number 600-000-966 Ver. 3                                                                                                                                                             

7

Description 

Read/

Write

Variable Name 

Data 

Type

LONworks 

SNVT

Cooling Utilization Over Last 
Hour -Percentage of cooling is 
used in the last hour of 
operation; this point applies to 
DX unit. 

R Comp_duty 

I nvoCoolUtlz  8 

Heating Utilization Over Last 
Hour -Percentage of heating is 
used in the last hour of 
operation 

R Heat_duty 

I nvoHeatUtlz  8 

Humidifier Utilization Over Last 
Hour -Percentage of humidifier 
is used in the last hour of 
operation 

R Hum_duty 

I nvoHumUtlz  8 

Compressor 1 Runtime -This 
point applies to DX unit with one 
compressor -high 

R C1_Hours_H 

I nvoC1_Hours_H 

Compressor 1 Runtime -This 
point applies to DX unit with one 
compressor -low 

R C1_Hours_L 

I nvoC1_Hours_L 

Compressor 2 Runtime -This 
point applies to DX unit with 
dual compressor - high 

R C2_Hours_H 

I nvoC2_Hours_H 

Compressor 2 Runtime -This 
point applies to DX unit with 
dual compressor - low 

R C2_Hours_L 

I nvoC2_Hours_L 

Heater 1 Runtime - high 

Ht1_Hours_H 

nvoHt1_Hours_H 

Heater 1 Runtime - low 

Ht1_Hours_L 

nvoHt1_Hours_L 

Humidity upper limit alarm 

Write 
only 

Hum_Hi_SP I 

nviHiHumLimit 

Upper limit alarm of return air 
temp 

Write 
only 

Ret_Air_Hi_SP I 

nviHiTempLimit 

105 

Humidity setpoint 

R/W 

Hum_setpoint 

nvoHumSetpoint / 
nviHumSetpoint 

CW valve open % (0-100% with 
10% increment) 

R CW_disp 

I nvoValve 

Chilled Water Utilization Over 
Last Hour - This applies to 
Chilled water or Energy saver 
units. 

R WtrVlv_duty 

I nvoChillUtlz  8 

Humidifier Runtime - high 

Hum_Hours_H 

nvoHum_Hours_H  8 

Humidifier Runtime - low 

Hum_Hours_L 

nvoHum_Hours_L  8 

Blower Runtime - high 

Blower_Hours_H 

nvoFan_Hours_H  8 

Blower Runtime - low 

Blower_Hours_L 

nvoFan_Hours_L 

Summary of Contents for LonWorks dap4

Page 1: ...Data Aire dap4 LonWorks Interface Instructions Data Aire Inc 230 West BlueRidge Ave Orange CA 92865 Document number 600 000 966 April 2014 Revision 3 0 ...

Page 2: ...number 600 000 966 Ver 3 2 Table of Contents 1 Introduction 3 2 Physical channels 3 3 Layout of the boards 3 4 Meanings of the LEDs 3 5 Installation 4 6 Connection to the LonWorks network 5 7 XIF and NXE file for dap4 6 8 dap4 LonWorks Point list 6 ...

Page 3: ...hout any restrictions in the topology that is star ring on one bus only or with any combination of these Communication speed 78 125 kbps Maximum distance Belden 85102 cable 500m for connections between the nodes with free topology 3 Layout of the boards Fig 1 LonWorks card 1 Connector to the dap4 controller BMS card 2 Terminal block for LonWorks network GND A B 3 Service pin 4 Green service LED 5 ...

Page 4: ...their original package as long as possible If necessary take the controller from its package and place it into antistatic packaging without touching the back of the board Absolutely avoid non antistatic plastic bags polystyrene or sponges Do not pass the electronic components or boards directly to other operators to prevent electrostatic induction and discharges Connect Lonworks card to the dap4 o...

Page 5: ...rroneous data Service pin To activate the service pin simply momentarily short circuit the two pins on the board see Fig 1 and no 3 with the tip of a screwdriver or a similar tool The service pin must only be activated during the installation of the node When the pin is activated the node sends a broadcast message over the LonWorks network containing the information required for identification The...

Page 6: ...Maximum A nvoHiTempHistory 105 Minimum Return air temp in last 24hrs R Minimum A nvoLoTempHistory 105 Temperature setpoint R W Temp_Setpoint A nvoTempSetpoint nviTempSetpoint 105 Temperature of chilled water R CW_Tmp A nvoWaterTemp 105 Temperature of discharge air R Disch_Air_Tmp A nvoDischTemp 105 Value of the analog input 1 R Opt1_Analog A nvoOpt1_Analog 8 Value of the analog input 2 R Opt2_Anal...

Page 7: ... Compressor 2 Runtime This point applies to DX unit with dual compressor high R C2_Hours_H I nvoC2_Hours_H 8 Compressor 2 Runtime This point applies to DX unit with dual compressor low R C2_Hours_L I nvoC2_Hours_L 8 Heater 1 Runtime high R Ht1_Hours_H I nvoHt1_Hours_H 8 Heater 1 Runtime low R Ht1_Hours_L I nvoHt1_Hours_L 8 Humidity upper limit alarm Write only Hum_Hi_SP I nviHiHumLimit 8 Upper lim...

Page 8: ... 83 No air flow alarm R Air_Flow_alm D Alarm_1 Bit1 83 Dirty filter from digital input R Filter_alm D Alarm_1 Bit2 83 Alarm from humidifier digital input R Humidifier_alm D Alarm_1 Bit3 83 Temperature of return air above firestat alarm set point R Firestat_alm D Alarm_1 Bit4 83 One or more comps has short cycled R Shortcycle_alm D Alarm_1 Bit5 83 Loss of power requires manual reset of alarm R PwrU...

Page 9: ... door Optional alarm External alarm input required R SeeTag_cust_alm3 D Alarm_2 Bit8 83 Local alarm 4 See tag inside door Optional alarm External alarm input required R SeeTag_cust_alm4 D Alarm_2 Bit9 83 Standby pump on Check primary pump Optional alarm Pump failure input signal required R Stdby_Pump_On D Alarm_2 Bit10 83 Alarm UPS power on Check main power Optional alarm External alarm input requ...

Page 10: ...Alm D Alarm_3 Bit4 83 High condensation from digital input R Condensation_alm D Alarm_3 Bit5 83 Unit in standby all functions held off Optional alarm Control input signal required Factory setting required R Unit_In_Standby D Alarm_3 Bit6 83 Cooling operation inhibited by BMS R W BMS_Cooling_inhibit D nvoBMSCool_In nviBMSCool_In 95 Heat inhibited due to bms R W BMS_Heat_inhibit D nvoBMSHeat_In nviB...

Reviews: