Dap4 LonWorks Interface Instructions 

Document number 600-000-966 Ver. 3                                                                                                                                                             

4

  Remains on for one second when receiving a wink command via the network 

(see 

Connection to the LonWorks

® 

network

). 

 

   

The red fault LED: 

  Signals problems in the connection between the board and the dap4 controller. 

 
WARNING 

If the red LED comes on, make sure the instructions described under 

Installation 

have 

been carefully followed. Network address must be greater than 1 (Use screw driver and 
press button next to J3 connector to display the network address) and protocol must be 
set to Lon on dap4 network config menu. 

 

5. Installation 

IMPORTANT WARNINGS

: precautions in handling the board. Electrical damage 

may occur to the electronic components as a result of electrostatic discharges from 
the operator. Suitable precautions must be therefore be taken when handling these 
components

, specifically: 

 

  Before handling any electronic component or board, touch an earthed object 

(simply not touching the component is not enough to prevent a spike, as static 
electricity can produce a 10000V discharge, which can form an arc of about 
1cm). 

  All materials must be kept inside their original package as long as possible. If 

necessary, take the controller from its package and place it into antistatic 
packaging, without touching the back of the board; 

  Absolutely avoid non-antistatic plastic bags, polystyrene or sponges; 

  Do not pass the electronic components or boards directly to other operators (to 

prevent electrostatic induction and discharges). 

   

Connect Lonworks card to the dap4 or Mini-dap4  

With reference to Figs. 2- 5 below, insert the board in the dap4 or Mini-dap4 as 
follows: 
1.  Disconnect the power supply to the controller. 
2.  Using a screwdriver, remove the BMS card cover (

serial card 

cover on Mini-

dap4) (see Fig. 2). 

3.  With cutting nippers, remove the pre-cut plastic part from the cover, thus making 

the opening for the 3-pin connector (see Fig. 3). 

4.  Insert the LonWorks card in the corresponding plug-in connector, initially holding 

it diagonally and then making sure it is properly inserted and pushed up against 
the two plastic supports on the case of the dap4 (see Fig. 4); 

5.  Close the cover again, aligning the connector on the card with the hole made in 

the cover (see Fig. 5). 

6.  Reconnect the power supply to the controller; if the BMS 1 communication port 

has been set to use the Lon protocol, the red LED on the board will come on for 
a few seconds and then will go off immediately, indicating correct operation. 
 
 
 
 
 

Summary of Contents for LonWorks dap4

Page 1: ...Data Aire dap4 LonWorks Interface Instructions Data Aire Inc 230 West BlueRidge Ave Orange CA 92865 Document number 600 000 966 April 2014 Revision 3 0 ...

Page 2: ...number 600 000 966 Ver 3 2 Table of Contents 1 Introduction 3 2 Physical channels 3 3 Layout of the boards 3 4 Meanings of the LEDs 3 5 Installation 4 6 Connection to the LonWorks network 5 7 XIF and NXE file for dap4 6 8 dap4 LonWorks Point list 6 ...

Page 3: ...hout any restrictions in the topology that is star ring on one bus only or with any combination of these Communication speed 78 125 kbps Maximum distance Belden 85102 cable 500m for connections between the nodes with free topology 3 Layout of the boards Fig 1 LonWorks card 1 Connector to the dap4 controller BMS card 2 Terminal block for LonWorks network GND A B 3 Service pin 4 Green service LED 5 ...

Page 4: ...their original package as long as possible If necessary take the controller from its package and place it into antistatic packaging without touching the back of the board Absolutely avoid non antistatic plastic bags polystyrene or sponges Do not pass the electronic components or boards directly to other operators to prevent electrostatic induction and discharges Connect Lonworks card to the dap4 o...

Page 5: ...rroneous data Service pin To activate the service pin simply momentarily short circuit the two pins on the board see Fig 1 and no 3 with the tip of a screwdriver or a similar tool The service pin must only be activated during the installation of the node When the pin is activated the node sends a broadcast message over the LonWorks network containing the information required for identification The...

Page 6: ...Maximum A nvoHiTempHistory 105 Minimum Return air temp in last 24hrs R Minimum A nvoLoTempHistory 105 Temperature setpoint R W Temp_Setpoint A nvoTempSetpoint nviTempSetpoint 105 Temperature of chilled water R CW_Tmp A nvoWaterTemp 105 Temperature of discharge air R Disch_Air_Tmp A nvoDischTemp 105 Value of the analog input 1 R Opt1_Analog A nvoOpt1_Analog 8 Value of the analog input 2 R Opt2_Anal...

Page 7: ... Compressor 2 Runtime This point applies to DX unit with dual compressor high R C2_Hours_H I nvoC2_Hours_H 8 Compressor 2 Runtime This point applies to DX unit with dual compressor low R C2_Hours_L I nvoC2_Hours_L 8 Heater 1 Runtime high R Ht1_Hours_H I nvoHt1_Hours_H 8 Heater 1 Runtime low R Ht1_Hours_L I nvoHt1_Hours_L 8 Humidity upper limit alarm Write only Hum_Hi_SP I nviHiHumLimit 8 Upper lim...

Page 8: ... 83 No air flow alarm R Air_Flow_alm D Alarm_1 Bit1 83 Dirty filter from digital input R Filter_alm D Alarm_1 Bit2 83 Alarm from humidifier digital input R Humidifier_alm D Alarm_1 Bit3 83 Temperature of return air above firestat alarm set point R Firestat_alm D Alarm_1 Bit4 83 One or more comps has short cycled R Shortcycle_alm D Alarm_1 Bit5 83 Loss of power requires manual reset of alarm R PwrU...

Page 9: ... door Optional alarm External alarm input required R SeeTag_cust_alm3 D Alarm_2 Bit8 83 Local alarm 4 See tag inside door Optional alarm External alarm input required R SeeTag_cust_alm4 D Alarm_2 Bit9 83 Standby pump on Check primary pump Optional alarm Pump failure input signal required R Stdby_Pump_On D Alarm_2 Bit10 83 Alarm UPS power on Check main power Optional alarm External alarm input requ...

Page 10: ...Alm D Alarm_3 Bit4 83 High condensation from digital input R Condensation_alm D Alarm_3 Bit5 83 Unit in standby all functions held off Optional alarm Control input signal required Factory setting required R Unit_In_Standby D Alarm_3 Bit6 83 Cooling operation inhibited by BMS R W BMS_Cooling_inhibit D nvoBMSCool_In nviBMSCool_In 95 Heat inhibited due to bms R W BMS_Heat_inhibit D nvoBMSHeat_In nviB...

Reviews: