Daspi PIXELP Instruction Manual Download Page 7

Programming with barrier using just limit switches (dip4 ON), slowing down is set from the limit switches this time; only for old Punto 24.

SET PLASTIC CAMS IN THE WAY THEY TRIGGER THE SWITCHES BEFORE THE LEVER HITS THE MECHANICAL STOPPERS, BOTH IN OPENING AND CLOSING. 

IMPORTANT : close the barrier (boom horizontal position and limit switches on closing engaged), led DL10 must be ON.

1. 

NO

 NEED to press 

PGRM

 button

2. Give a 

1° START

 command (or remote control command previously stored as in the instructions), the gate opens.

3. When limit switch in opening is triggered (

DL11

 light up), barrier starts slowing down until hits the opening stopper.

4. Give a

 2° START

 command, barrier starts closing.

5. When limit switch in closing is triggered (

DL10

 light up), barrier starts slowing down until hits the closing stopper.

HOW TO CHANGE THE BOOM’S OPENING WAY

The barrier is 

ALWAYS

 sold with the boom mounted on its right side looking the barrier from the front main door. 

If you want to change the opening way, do as follows:

Hang the springs on the other side of the lever – invert motor wirings T1 with T2 – invert limit switches wirings 10 with 11

ADJUSTMENT:

• Operating trimmers 

CL PWR - OP PWR

 are for adjusting the torque, in order to make the barrier stop as required by regulations and carry out the necessary 

measurements. 

• Exceeding the set torque level will make the anti- crushing feature intervene: while closing the barrier reverses the movement until complete opening, during 

opening it reverses the movement for about 1 sec. and it stops. Attention! In case of intervention for 3 consecutive times of anti-crushing feature during closing, 

the barrier will remain open and the automatic closing (if activated) will be disabled. It is now required a start command to close the barrier.

• Set the length of the pause time using trimmer TCA (from 1 to 120 seconds)

Give information to people involved in the use of the gate about operations and commands, safety devices and any danger arising from the use of the automation. 

Fill in the technical installation file and comply with current regulations.

USUAL TROUBLES

During Programming, barrier STARTS closing

Invert motors wires t1-t2 and verifying limit switches wirings as well

Barrier doesn’t close

Check led dl7 ( must be off) and photocells wirings as well. Led dl3 must be off. If 

I close the contact on OPEN, barrier should open (if it was closed) as long as the 

contact OPEN will be reopened.

Photocells don’t work

Check photocells wirings ( respecting photocells positive and negative) . Eventually 

take off photocells synchronism jumper. If you are using Phototest feature, check 

that power supply goes into input 13 negative and 12 positive (with this feature when 

barrier is still, DL7 is ON; it switches off when barrier moves)

Barrier ricloses after 3 sec. even though TCA is deactivated  and photocells were 

not engaged

It is set the feature “Close after passing through photocells” (dip3 ON) and power 

supply is wired into output 12-13. Move power supply wirings into 13-14 or deactivate 

feature “Close after passing through photocells”

Barrier doesn’t open at all

Check DL8 (must be OFF), safety edge input

Remote control can not be stored into the receiver

Arase the whole memory from the receiver throughout key DEL/PED and try to restore 

the remote. Check also remote control function.

Barrier opens completely and then closes for about 1 sec.

Anticipate  the trigger of electric limit switches in opening

Barrier opens without slowing down.

Anticipate  the trigger of electric limit switches in opening  and reprogramm the 

control panel.

Barrier closes and once it touches the mechanical stopper it reopens

Anticipate  the trigger of electric limit switches in closing  and reprogramm the 

control panel

While opening, barrier stops and closes for about 1 sec.

Increase power on opening,  trimmer op pwr

While closing, barrier stops and reopens completely

Increase power on closing, trimmer  cl pwr

LED1-2 ON with steady light

Erase the whole memory from the receiver throughout key DEL/PED and try to restore 

the remotes

Flashing light stays on with fix light and barrier remains open

Barrier has detected for 3 times continuously while closing and obstacle. Increase 

power on closing by  trimmer cl pwr

Lack of tension 24vdc in the inputs 14-13 

These inputs can supply  max 150ma; if you need more than this, use inputs 13 

negative and 15 positive with max. tension 500ma

Summary of Contents for PIXELP

Page 1: ...Vdc max 120W Centrale de commandes pour barri res 24 Vdc max 120W VER II 2012 J1 TCA SW1 CL PWR OP PWR RX433 DL1 DL2 START PRGM INS DEL PED DL3 DL4 DL6 DL7 DL8 DL10 DL11 1 2 3 4 5 6 LED1 LED2 F1 J2 T1...

Page 2: ...li dopo aver alimentato la centrale DL1 Led di colore rosso segnala l utilizzo del pulsante START inserito sulla scheda da usare nel caso si necessitasse di un comando prima di aver inserito i telecom...

Page 3: ...CA al massimo 15 17 Uscita luce semaforo DIP5 ON accesa a barriera completamente aperta 24Vdc max 10W 8 9 Ingresso COSTA interviene solo in apertura arresta la barriera e chiude per 1secondo 18 19 Ing...

Page 4: ...orario funzione di richiusura a tempo disattivata Istruire il personale addetto all uso dell automazione sui relativi comandi dispositivi di sicurezza e pericolosit derivante dall uso dell automazione...

Page 5: ...vated LED TABLE DL1 Red LED to indicate use of START button command on control panel DL8 Red LED lights up when the SAFETY EDGE contact opens DL2 Red LED indicates the programming input mode and the v...

Page 6: ...ergy saving while barrier is still and mandatory in order to use feature PHOTOTEST DIP6 ON max 150mA J2 Connector for secondary input of the transformer 24 Vac 6 PROGRAMMING It must be carried out aft...

Page 7: ...uring Programming barrier STARTS closing Invert motors wires t1 t2 and verifying limit switches wirings as well Barrier doesn t close Check led dl7 must be off and photocells wirings as well Led dl3 m...

Page 8: ...limentado la central DL1 Led de color rojo se aliza el uso del pulsador START presente en la tarjeta se debe utilizar en caso de que se necesite un control antes de haber memorizado los controles remo...

Page 9: ...nciona solo cuando la barrera abre para la barreraylacierrapor1seg 18 19 Conector ENCODER 9 10 Entrada para el final de carrera de cierre Contacto N C T1 T2 Salida del motor 24 Vdc 9 11 Entrada para e...

Page 10: ...sa interviniendo en el trimmer TCA de 1 hasta max 120 segundos Para poner en cero el tempo girar completamente en el sentido del reloj el trimmer Instruir al personal encargado para el uso de la autom...

Page 11: ...le une anomalie le clignotant reste allum et la barri re ne d marre pas Fonction non active Led indiquant l tat des entr es de la carte v rifiables apr s avoir r tabli l alimentation de la centrale DL...

Page 12: ...dant le mouvement d ouverture il n intervient pas Avec DIP3 ON si la photocellule est occup e pendant le mouvement ou avec la barri re toute ouverte le temps de fermeture automatique devient 3 seconds...

Page 13: ...si active est d sactiv e Une commande start est alors n cessaire pour refermer la barri re R gler la dur e du temps de pause en agissant sur le potentiom tre TCA de 0 120 secondes en le tournant tout...

Page 14: ...NOTES...

Page 15: ......

Page 16: ...e cancelli S r l se r serve le droit d apporter toutes les modifications qu elle juge bonnes pour am liorer les produits pr sents dans ce manuel Les illustrations et les photographies sont purement in...

Reviews: