CODE  FAULT EVENT 

ALARM 

ICON 

SOLUTION 

24 

Battery type is wrong 

None 

 

1.

 

Set the correct battery type according to the battery installed to the system. 

2.

 

Reboot the inverter. If the error remains, contact your installer. 

 
Note: For third-party lithium batteries, battery type should be set as Lead Acid. 

25 

RCMU test fault 

None 

 

Reboot the inverter. If the error remains, contact your installer. 

26 

Model setting fault 

None 

 

Reboot the inverter. If the error remains, contact your installer. 

27 

Battery Voltage Drop 
[Battery voltage dropped below 30V] 

None 

 

1.

 

Check the battery BMS errors and the wiring. 

2.

 

Reboot the inverter. If the error remains, contact your installer. 

28 

Battery wake up fault 
[The system tried to wake up the 
battery but failed.] 

None 

 

1.

 

Turn off the inverter. 

2.

 

Check the battery voltage. 

3.

 

Check the battery breaker and wiring. 

4.

 

Check the battery communication cable. 

5.

 

Turn on the inverter. If the error remains, contact your installer. 

 

 

On the Power Flows Page, the 

  icon will flash when there is a warning. Below are warning codes and their solutions. 

CODE   WARNING 

ICON 

SOLUTION 

53 

Stacking Canbus communication error 

 

1.

 

Turn off the inverter. 

2.

 

Check the canbus communication cables. 

3.

 

Turn on the inverter. If error remains, contact your installer. 

54 

Power island 

 

1.

 

For warning 55. If the Utility is down, wait for it to come back on. 

2.

 

Reboot the inverter. 

3.

 

The inverter will wait for 5 minutes before attempting to connect to the Grid. 

4.

 

If the warning remains, contact your installer. 

55 

Grid is disconnected 

 

56 

Grid voltage exceeds the upper threshold 

 

57 

Grid voltage falls below the lower threshold   

 

58 

Grid frequency exceeds the upper threshold 

 

59 

Grid frequency falls below the lower threshold 

 

61 

Battery voltage is too low 
[Battery voltage is less than 44V (lead-acid) or 
SOC is lower than 10% (Lithium)] 

 

Wait for the Grid or PV to charge the battery. Warning code will change to 62 once the battery 
voltage is above 44V or the SOC is above 10%. 
 
Note: Battery cannot be discharged, and system output can only come from the Grid. 

62 

Low battery SOC level 
[The battery SOC is less than the battery 
reserve] 

 

Wait for the Grid or PV to charge the battery. Once the SOC reaches 20% above the battery 
reserve, the warning will be cleared. 
 
Notes: 
If the Grid is absent, the battery can be discharged. 
If the Grid is present, the battery can be discharged if SOC is above the battery reserve. 

63 

Battery is not detected 

 

1.

 

Turn off the inverter. 

2.

 

Make sure the battery is on. 

3.

 

Check battery connection for any loose wiring. 

4.

 

Turn on the inverter. If error message remains, contact your installer. 

64 

Inverter output OCP 

 

1.

 

Inverter output current exceeds the upper threshold. 

2.

 

Reboot the inverter. If error remains, contact your installer. 

 
Alarm – On: 1s, Off: 1s 

65 

RS485 communication error 

 

1.

 

Turn off the inverter and check all communication wires. 

2.

 

Turn on the inverter. If error remains, contact your installer. 

66 

Output derated 
[When system temperature is too high, the 
output power has been derated.] 

 

1.

 

Make sure the inverter is properly ventilated and the fans are free of debris.   

2.

 

If possible, lower the load or ambient temperature. 

 
Notes: 
System output lowered to 60% when the system temperature is higher than 85°C. 
System output lowered to 80% when the system temperature is higher than 80°C. 
System output restored to 100% when the system temperature is lower than 70°C. 

67 

Off Grid Operation 

 

Grid is present, but system is in off-grid mode via remote command. 

68 

Peak Shaving Over Power 

 

Grid power usage has reached the Peak Shaving Power threshold. 

69 

Generator mode 

 

The grid is not present, and the inverter is receiving power from the generator. 

70 

Generator Reverse Feed 

 

Power is feeding back to the generator. If the inverter is setup to have remote control over the 
generator, the inverter will turn off the generator. 

71 

Battery voltage Inconsistent 

 

Battery voltage measured by the inverter is not consistent with the BMS value. 

 

 

Summary of Contents for H5001

Page 1: ...INSTALLATION MANUAL H5001 HYBRID INVERTER...

Page 2: ...rs 8 Battery Charging Requirements 9 Communication Ports 9 Access Panel 10 TURNING THE SYSTEM ON OFF 11 Turning On the System 11 Turning Off the System 11 OPERATION AND DISPLAY PANEL 12 Display Overvi...

Page 3: ...enance or cleaning or working on any circuits connected to the inverter Turning off controls will not reduce this risk Internal capacitors can remain charged for 5 minutes after disconnecting all sour...

Page 4: ...UNCTION Piston Breakers For Over Current Protection of Grid L1 L2 Dip Switches For Firmware Update Jumpers For Firmware Update USB B For Computer Connection Communication Ports Power Switch Battery Br...

Page 5: ...ution Degree rating The unit is for indoor applications only and must be mounted in a protected area that is dry free of excessive dust and has adequate air flow CAUTION The inverter is heavy 87lb 40k...

Page 6: ...d 5 Time Of Use Low electricity cost Operate as Back up mode High electricity cost Operate as Residential mode 6 Time Of Use With Battery Feed In Low electricity cost Operate as Back up mode High elec...

Page 7: ...se power surges that exceeds the inverter specifications When the grid is present the inverter can accept power surges up to 7 5kW for 30 seconds When the grid is absent the inverter can accept power...

Page 8: ...ng or modifying any connections To prevent the risk of electric shock make sure the ground wire is properly earthed before operating this unit whether the grid is connected or not To reduce the risk o...

Page 9: ...communication battery communication external display connection and parallel operation The ports are located inside the distribution box on the top bulkhead panel PORT FUNCTION RJ45 For External Displ...

Page 10: ...r Over Current Protection There are three circuit breakers that protect the Grid path One circuit breaker is in the distribution box and is rated at 40A The piston breakers are for Grid L1 L2 and are...

Page 11: ...e battery Refer to the battery s instruction manual Turn on the grid breaker if grid is connected Turn on the Power Switch Wait for system bootup and the fans to turn on plus 3 beeps Turn on the Load...

Page 12: ...ction Exits setting mode Previous page previous item or decrease number ICON DESCRIPTION Represents the PV Array Represents the Battery Pack Represents the Utility Represents the Load Represents the H...

Page 13: ...d use the key to set it When done press the key You will see a message stating the settings are being updated When you see Setting OK message press any key Manually restart the inverter using the Powe...

Page 14: ...AC breakers must be sized for 40A or less and 2 all wiring must be sized for 40A or more The following diagram shows how the distribution box is electrically connected to the hybrid inverter NOTES Th...

Page 15: ...If the error remains turn off the Utility and the inverter s Grid breaker Then measure the Grid and make sure the impedance of L1 L2 and N relative to ground and to each other should be an open circui...

Page 16: ...the Grid or PV to charge the battery Warning code will change to 62 once the battery voltage is above 44V or the SOC is above 10 Note Battery cannot be discharged and system output can only come from...

Page 17: ...7000W 20ms Input Voltage Limits Bypass L L 180 to 280V 240V nominal Input Frequency Range Bypass 45 to 54 9Hz 55 to 65 Hz AC OUTPUT TO GRID GRID SUPPORT Output Power Continuous 25 C 5000W Grid Sell C...

Page 18: ...e connecting the 4 pin terminal block in the inverter s AUX GEN board Wiring the Current Sensor Make sure inverter s hardware version is 2 or above CTs cannot be installed with inverter hardware versi...

Page 19: ...step 5 Remove the access panel and locate the emergency port Insert the 2 pin connector from the emergency button into the emergency port then skip to step 7 Remove the white 2 pin connector from the...

Page 20: ...ing the button down pull the safety cover away Reset the emergency button Rotate button clockwise The button will pop back to the starting position Reset the safety cover Push the top section of the s...

Page 21: ...trademarks of Darfon Electronics Corp All other trademarks are the property of the respective owners Manufactured by Darfon Electronics Corp 167 Shan ying Road Gueishan Taoyuan 333 Taiwan R O C Tel 88...

Reviews: