1.2.1
Output type
3
Service
3.2
Voltages
3.4
Reset settings
3.3
Information
3.5
Turn off
3.1
Failure code
2
Settings
2.1.2
GCKV
2.3.2
Hour
2.5.2
Backlight
2.1.3
TH/THP
2.3.3
Time correct.
2.5.3
Backlight time
2.2
Sensor type
2.4
Language
2.6
Sound
2.3
Time
2.5
Display
2.7
Temp. Correct.
2.1
Device type
2.1.1
ANeco
2.3.1
Date
2.5.1
Contrast
MENU
1
Parameters
1.2.2
V(minimum)
1.2.3
T(maximum)
1.2.4
V(maximum)
1.2.5
Temp. Correct.
1.3.1
Rotation speed
1.4.1
Working days
1.4.2
Saturdays
1.4.3
Sundays
1.1
Operating mode
1.2
Sensor mode*
1.3
Constant mode
1.4
Zone mode
1.2.1
T(minimum)
ANALOG SENSOR
DIGITAL SENSOR
EN
Figure 4 legend:
turning the knob right
turning the knob left
knob briefly pressed
knob pressed and held
* the screen is displayed only if one of the external sensors was selected
1. PARAMETERS
Parameter configuration of the controlled device regulator.
1.1 Operating mode
Selection of working mode of the regulator:
sensing
- the rotation speed of the controlled device depends on parameters
set in sub-menu 1.2. This item is visible if the type of the external sensor
was selected in menu 2.2 - “analogue”.
constant
- the rotation speed of the controlled device is constant and
depends on parameters set in sub-menu 1.3.
zoned
- the rotation speed of the controlled device is constant during the
given period and depends on parameters set in sub-menu 1.4.
const. sens.
- the rotation speed of the controlled device is constant and
depends on parameters set in sub-menu 1.3, but only when the sensor is
active - otherwise the device will be switched off. This item is visible if the
type of the external sensor was selected in menu 2.2 - “digital”.
zone sensing
- the rotation speed of the controlled device is constant during
the given period and depends on parameters set in sub-menu 1.4, but
only when the sensor is active - otherwise the device will be switched off.
This item is visible if the type of the external sensor was selected in menu
2.2 - “digital”.
1.2 Sensor mode
Parameter configuration of the sensor mode of the regulator (this item is
visible if the type of the external sensor was selected in menu 2.2).
If an external analogue sensor was selected:
1.2.1 T (minimum)
- Temperature setting, at which the controlled device is
switched on with a rotation speed equal to V(minimum).
(0 ÷ +55°C)
1.2.2 V (minimum)
- Minimum rotation speed setting of the controlled device.
(0 ÷ 50%)
1.2.3 T (maximum)
- Temperature setting, at which the controlled device
reaches its maximum rotation speed equal to V(maksimum).
(+60 ÷ +100°C)
1.2.4 V (maximum)
- Maximum rotation speed setting of the controlled device.
(50 ÷ 100%)
1.2.5 Temp. Correct.
- Temperature correction setting of an external
analogue sensor.
(-30 ÷ +30°C)
If an external digital sensor was selected:
1.2.1 Output type
Selection of the output type of the external digital sensor.
NC - normally closed.
NO - normally open.
1.3 Constant mode
Parameter configuration of the fixed mode of the regulator.
1.3.1 Rot. speed
- Rotation speed setting of the controlled device.
(0 ÷ 100%)
1.4 Zone mode
Parameter configuration of the zone mode of the regulator.
1.4.1 Working days
- Setting time zones used on working days.
S1 (00:00 ÷ 23:56 / 0 ÷ 100%)
S2 (S1 ÷ 23:57 / 0 ÷ 100%)
S3 (22 ÷ 23:58 / 0 ÷ 100%)
S4 (S3 ÷ 23:59 / 0 ÷ 100%)
1.4.2 Saturdays
- Setting time zones used on Saturdays.
S1 (00:00 ÷ 23:56 / 0 ÷ 100%)
S2 (S1 ÷ 23:57 / 0 ÷ 100%)
S3 (22 ÷ 23:58 / 0 ÷ 100%)
S4 (S3 ÷ 23:59 / 0 ÷ 100%)
1.4.3 Sundays
- Setting time zones used on Sundays.
S1 (00:00 ÷ 23:56 / 0 ÷ 100%)
S2 (S1 ÷ 23:57 / 0 ÷ 100%)
S3 (22 ÷ 23:58 / 0 ÷ 100%)
S4 (S3 ÷ 23:59 / 0 ÷ 100%)
MENU
Figure 4.
Organization of the menu.