Possible malfunctions and their correction
 

The device is equipped with fuses. The fuse blows in case of an internal failure and for fire prevention. After 
detection of the malfunction cause it is necessary to replace the fuse. Never replace a fuse with a bigger one.

9

Malfunction

Cause

Solution

Controller is improperly connected or
not connected to power line 

Check wiring with wiring diagram

No information on the

display

High or low electric line voltage

Connect the device to a power source
with required parameters

The display is blinking

Power cable is damaged 

Replace the cable

A.  No voltage in the electric line
B. F

  use is blown

С. Power cable is not connected

A.  Check the electric line voltage 
B. R

  eplace the fuse

С. Connect the power cable 

Power indicator is off

The device repair and diagnostics must be performed in an authorized service center.

Attachment 

The device is switched on

but there is no mist 

Voltage is more than 5% lower/higher
than required 

Check the voltage, install a stabilizer
if necessary

Water tank overflow

A.  Float valve is incorrectly adjusted 
B. Float valve is blocked or damaged 

A.  Adjust the float valve 
B. Clean or replace the float valve 

Water mist is thin

or no mist at all

A.  Float valve incorrect level 
B.  Badly contaminated radiator panel
C. Voltage is more than 5% lower than
required

A.  Adjust the float valve level in
accordance with instructions 
B.  Clean or replace the panel
C. Install a stabilizer

Replace the humidity sensor

Check the wires for discontinuity oк for
insulation damage

After checking of the sensor check
whether it is installed in a right way

Install the sensor in accordance with
instructions

Find and remove the source
of disturbances

Check wiring with wiring diagram

Set correct parameters

Replace the humidity controller

Humidity sensor is broken

Humidity sensor wires are damaged

Humidity sensor installation depth
is not sufficient

Humidity sensor is installed in

a wrong place

There is a source of strong
disturbances near the device

Controller wires are is improperly
connected

Incorrect operating parameters

Humidity controller is broken 

Device misoperation

Device misoperation

Summary of Contents for HUM-S Series

Page 1: ...HUM S series Ultrasonic humidifiers Operation manual...

Page 2: ...R www danvex fi...

Page 3: ...instructions 3 Component parts 3 Intended use of the product 4 Operation principle 4 Product design 5 Dimensions and weight 6 Technical specifications 6 Installation 6 Commissioning 7 Maintenance 8 Tr...

Page 4: ...ted in explosion hazardous premises Before opening any enclosure panels it is necessary to de energize the humidifier The panels should always be closed except for the time when maintenance works are...

Page 5: ...lming for environmental simulation fog smoke of gunfire etc Operating principle Ultrasonic humidification principle is based on two effects superposition 1 Capillary wave theory Ultrasonic generators...

Page 6: ...epair of the humidifier electrical components Top removable panel used for maintenance of piezoelectric transducers and float valve system Steam pipe socket used for connection of the output steam pip...

Page 7: ...be not more than 20 Pa for models HUM 3S HUM 6S and not more than 40 Pa for other models For better water mist distribution inside a room it is necessary to use a steam pipe with diffusers In this ca...

Page 8: ...position switch located on the right side panel Before the operating mode selection it is necessary to open the water supply and to wait till the humidifier tank is filled with water The humidifier h...

Page 9: ...tors free of any deposits It is prohibited to use household detergents for tank and radiator panel cleaning Do not touch the nozzles Cleaning should be carried out at least 1 time per month Proceed as...

Page 10: ...eck the voltage install a stabilizer if necessary Water tank overflow A Float valve is incorrectly adjusted B Float valve is blocked or damaged A Adjust the float valve B Clean or replace the float va...

Page 11: ......

Reviews: