Commissioning 

Start up procedures

:

1. 

Make sure the dehumidifier is disconnected from the power supply source and that its main 

switch is in 

 

OFF position

.

2. 

Open the dehumidifier service panels and make sure there are no foreign matters inside 

the dehumidifier

.

3. 

Make sure all air throttles are opened and that channels are clean and not blocked

.

4. 

Make sure that air filters are installed and clean

.

5. 

Manually turn the fans impellers and make sure they rotate freely

.

6. 

Check the internal fuse.

7. 

Close the service panels and connect the dehumidifier to 

380/400

V power supply

8. 

S

witch on 

the dehumidifier power 

supply

. The following will be displayed on the control 

panel LCD

:

7

Dehumidified air

*

Rated air consumption
Pressure 

3

m

/

hour

Pa

10000

5

00

Parameter

Unit

Value

Reactivation air

*

Rated air consumption
Pressure 

3

m

/

hour

Pa

3500

250

Electric power and rated current

Total power
Voltage

 (

3

 

phase

,

 50 

Hz

)

kW

V

80

380/40

0

Reactivation air heater

Heater capacity
Heater type 

kW

-

70

Tubular Heating Element

Miscellaneous data 

Maximum sound pressure level
Operational temperatures range
Standard filter

:

 dehumidified air

R

   

eactivation air 

IEC protection, the whole dehumidifier  

dB(A)

о

С

-
-
-

65

–20…+

4

0

EU3
EU3

IP44

о

3

The above mentioned values are nominal based on the air temperature of 

20 С 

and the air density of

 1,2

kg

/

m

Summary of Contents for AD-10000

Page 1: ...DanVex AD 10000 Adsorption air dehumidifier Operation manual ...

Page 2: ...R www danvex fi 1 ...

Page 3: ...y instructions 3 Introduction 4 Purpose 4 Operation principle 4 Design 5 Dimensions and weight 5 Installation 6 Technical data 7 Commissioning 7 Maintenance 11 Transportation 12 Parts list 12 Attachment 13 Warranty obligations 16 2 ...

Page 4: ...r operate the units in the locations subject to explosion hazard Before opening any panels of the unit body it is required to disconnect the dehumidifier from the mains Before starting any maintenance works the dehumidifier should be out of operation for 15 minutes The unit s panels must be always closed except when the dehumidifier is being maintained The dehumidifier can be used for air drying a...

Page 5: ... The air flow to be dehumidified PROCESS AIR passes through the biggest sector The moisture from the air is trapped adsorbed by the rotor material The air leaves the rotor in dehumidified condition DRY AIR and is directed to a certain part of the building or a technological process where dehumidified air or a certain air humidity levels are required Since the rotor rotates slowly the incoming air ...

Page 6: ...ong service life The rotor manufacturing technology assures production of a product capable of saturated air processing without risk of destruction it means that the rotor can be used along with a precooler Besides the rotor will not be damaged even if the fan or the reactivation air heater fail to function Filters The dehumidifier is equipped with two filters One filter is located at the dehumidi...

Page 7: ... install the moist air duct upright it should be insulated and drain holes should be drilled in the lowest part of the elbow bend 2 4 mm Regeneration air duct The regeneration air duct should be as short as possible A metal net is installed at the duct input to prevent foreign matters entering the dehumidifier There is no need to insulate the duct The duct inclination angle is optional Dehumidifie...

Page 8: ...ct the dehumidifier to 380 400V power supply 8 Switch on the dehumidifier power supply The following will be displayed on the control panel LCD 7 Dehumidified air Rated air consumption Pressure 3 m hour Pa 10000 500 Parameter Unit Value Reactivation air Rated air consumption Pressure 3 m hour Pa 3500 250 Electric power and rated current Total power Voltage 3 phase 50 Hz kW V 80 380 400 Reactivatio...

Page 9: ...f the fans and the rotor continue operation for 5 10 minutes to prevent the overheating protection tripping 10 Press ESC to enter the setting menu Setting data 1 Enter temperature relative humidity and regeneration temperature by pressing or buttons till the required values are set Press ENTER 11 Press or for navigation correction of temperature and relative humidity range Press ENTER ...

Page 10: ...r there are two types of alarm signals the first type is used to announce about serious failures the second type is used to announce about minor problems In case of a serious problem a buzzer will sound the failure cause will be displayed on the screen and the dehumidifier will stop In case of a minor problem a buzzer will sound and the failure cause will be displayed on the screen An acoustic sig...

Page 11: ...R www danvex fi 10 ...

Page 12: ...on and disconnecting the power plug from the mains socket Filters The dehumidifier is equipped with two separate filters one for process air and one for regeneration air The filters are located in front of their appropriate inputs and are used for cleaning of the air entering the dehumidifier The filters cleaning and replacement intervals are based on the amount of dust and particles in the air at...

Page 13: ... the seals for damage and dust contamination Transportation Please observe the following rules of the dehumidifier transportation and storage Upon delivery it is required to check the dehumidifier for transportation damages The dehumidifier should be protected from rain and snow The dehumidifier should always be in upright condition It is not allowed to put heavy objects on the dehumidifier Rotor ...

Page 14: ...R www danvex fi 13 Attachment ...

Page 15: ...R www danvex fi 14 ...

Page 16: ...R www danvex fi 15 ...

Page 17: ...lies the Customer a repaired or a spare part Parts repair or replacement does not result in the warranty period extension The parts and components replaced under the warranty belong to DanVex DanVex or its distributor upon DanVex request has a right to inspect the defective parts and to check the correctness of the warranty claim Warranty repair execution conditions The damage occurred during the ...

Page 18: ......

Reviews: