Technical data of
AD-
100
00
Table
2
Commissioning
Start up procedures
:
1.
Make sure the dehumidifier is disconnected from the power supply source and that its main
switch is in
OFF position
.
2.
Open the dehumidifier service panels and make sure there are no foreign matters inside
the dehumidifier
.
3.
Make sure all air throttles are opened and that channels are clean and not blocked
.
4.
Make sure that air filters are installed and clean
.
5.
Manually turn the fans impellers and make sure they rotate freely
.
6.
Check the internal fuse.
7.
Close the service panels and connect the dehumidifier to
380/400
V power supply
.
8.
S
witch on
the dehumidifier power
supply
. The following will be displayed on the control
panel LCD
:
7
Dehumidified air
*
Rated air consumption
Pressure
3
m
/
hour
Pa
10000
5
00
Parameter
Unit
Value
Reactivation air
*
Rated air consumption
Pressure
3
m
/
hour
Pa
3500
250
Electric power and rated current
Total power
Voltage
(
3
phase
,
50
Hz
)
kW
V
80
380/40
0
Reactivation air heater
Heater capacity
Heater type
kW
-
70
Tubular Heating Element
Miscellaneous data
Maximum sound pressure level
Operational temperatures range
Standard filter
:
dehumidified air
R
eactivation air
IEC protection, the whole dehumidifier
dB(A)
о
С
-
-
-
65
–20…+
4
0
EU3
EU3
IP44
о
3
*
The above mentioned values are nominal based on the air temperature of
20 С
and the air density of
1,2
kg
/
m