40
Technical data
HCV7
The below table gives the technical data of the HCV7:
Specification
Unit
Data
Operating range DIBt*
m3/h
130 to 350
Operating range Passiv*
m3/h
130 to 320
Efficiency DIBt
%
85,7
Efficiency Passiv Haus
%
84,4
Efficiency EN 13141-7
%
84,6
Sound from cabinet (Passivhaus) 350 m3/h @ 100 Pa* LPA /LWA
50,1 dB(A)
Sound from ducts (Passivhaus) 350 m3/h @ 100 Pa*
LWA
64 dB(A)
Filters According EN779:2002 (Exhaust/Supply)
Class
G4/G4
(F7 option)
Installation surrounding temp.
°C
+12 to +50
Outdoor temp (without preheating installed)
°C
-12 to +50
Outdoor temp (with preheating installed)
°C
-25 to +50
Maximum humidity in extract air
g/m
3
10
CABINET:
Dimensions WxHxD.
mm
700x1050x750
Duct Connectors
mm
Ø200
Weight
kg
70
Insulation Lambda 0,031 W/mK
W/(m*K)
U<1
Drainage hose included
ø/length
¾” – 1m
Cabinet colour
RAL
9016
Fire classification, polystyrene
DIN 4102-1
Fire classification, unit
EN 13501-1:2002
ELECTRICAL:
Power input
V AC
230
Max. current consumption (without/with preheater )* Watt
234/1834
Max. power consumption (without/with preheater )*
Amp
0,73/7,98
Frequency
Hz
50
IP-classification
IP class
21
* Under Revision
Continued overleaf