1. Description of function
CDP 35T, 45T and 65T are working in accordance with the condensation principle. The humid air is drawn into the
unit by one, two or three fans. When passing through the evaporator the air is cooled down to below dew point and
water vapour is condensed into water, which is drained away. The now dry air is then passed over the condenser
coil where the air is heated. As a result of the released evaporator heat and the working energy of the compressor
being turned into heat energy, more heat is returned to the air than was previously extracted. This extra heat
corresponds to an approximate increase in temperature of 5ºC. The repeated circulation of air through the unit
reduces the relative humidity, giving very rapid but gentle drying.
1.1 Technical data
CDP 35T
CDP 45T
CDP 65T
Working area – humidity
%RH
40-100
40-100
40-100
Working area – temperature
ºC
10-36
10-36
10-36
Air volume at max. external pressure
m
3
/h
250
500
750
Power supply
V/Hz
1x230/50
1x230/50
1x230/50
Max. power consumption
kW
0,72
1,05
1,65
Max. ampere consumption
A
2,8
4,3
7,2
Refrigerant
R407C
R407C
R407C
Quantity of refrigerant
kg
0,6
0,95
1,6
Noise level* (1 m away from unit)
dB(A)
44
46
48
Weight
kg
57
68
95
Dimensions – H x L x W
mm
680 x 890 x 290 680 x 1200 x 290 680 x 1735 x 290
*Measured opposite to the duct openings
Warm humid air
Warmer and dehumidified air
Summary of Contents for CDP 35T
Page 37: ...35 8 El diagram Wiring diagram Schaltplan Sch ma lectrique CDP 35T 1 x 230V750Hz...
Page 38: ...36 El diagram Wiring diagram Schaltplan Sch ma lectrique CDP 45T 1 x 230V 50Hz...
Page 39: ...37 El diagram Wiring diagram Schaltplan Sch ma lectrique CDP 65T 1 x 230V 50Hz...
Page 43: ...41 CDP 35T 1 x 230V 50Hz 962452_a...
Page 45: ...43 CDP 45T 1 x 230V 50Hz 962453_a...
Page 47: ...45 CDP 65T 1 x 230V 50Hz 962454_a...
Page 48: ...46...
Page 49: ...47...
Page 50: ...48...
Page 51: ...49...