page 1 of 10
Oilbuner
Type Gulliver RG0.R
GB
Technical instructions
Main components of the oilburner,
dimensions
Type
367 T1
Terminal power – output
16,6 – 27,3 kW (H
i
) (1,4 – 2,3 kg/h)
Terminal power with special diffuser disc
21,3 – 36,7 kW (H
i
) (1,8 – 3,1 kg/h)
Fuel
Viscosity max. 6 mm
2
/s (1,5° E) at 20° C
Electrical supply
230 V +10% -10% 50 Hz
Electrical consumption
290 W
Capasitor
4 µF
Ignition transformer
Secondary: 8 kV 16 mA
Control box
550 SMD
Pump capacity
Maks. 30 kg/h at 10 bar
Pump pressure
8 – 15 bar
Approval
CE 00360272/99
1. Oil pump
2. Control box
3. Reset button
4. Boiler flange
5. Air-damper
6. Flange for nozzle holder
7. Photo resistance
K:\framen\instrukt\Dantherm\RG\Engelsk\RG0r\RG0R.fm-T1-020926-dm/lbk
Dimensions:
Main components of the oilburner: