PRECISIONAIR WS PRODUCT INFORMATION MANUAL
16
MAINTENANCE
|
SPARE PARTS
TEST COOLING CIRCUIT
The cooling circuit is designed for long
durability, and is based only on a few
components. Any testing of the circuit should
be conducted, only if, a relevant problem
has arisen. Open the unit’s outside cover, by
removing the two screws in the lower part.
Locate the service valve, connect a pressure
gauge, and check that the pressure is aligned
with the present temperature. Due to critical
refrigerant changes, low volume refrigeration
hoses with low loss fittings should be used
when accessing the refrigeration system. Care
should be taken to minimize any amount of
lost refrigerant.
SPARE PARTS
A number of spare and replacement parts
are available from Dantherm Cooling. Please
contact technical supprt for more information
at:
INSPECTION
The unit must be inspected before it is
reassembled and put back into service.
Please follow the steps below:
PHASE
DESCRIPTION
1
Are the fans clean and free of any corrosion?
2
Are the coolant pipes free of obstructions, damage, corrosion and show no obvious signs of
leakage?
3
Are the coils clean and undamaged?
4
Are all fan blades free of any obstructions, cracks or missing blades?
5
When manually rotating the fans, do the fans rotate freely, without vibrations and noise?
6
Is all wiring and insulation undamaged?
7
Are all connector secured properly and in good condition?
8
Inspect the drain hose (if any) for damage or obstruction.
9
Are there any alarms visible on the controller?