background image

44443-1098 <90-00059>

 P

AGE

 5

RCV and XMT Attenuator Circuits

The attenuator circuits are made up of resistance T-pads. The

pads are designed to be switched into the 4-wire RCV and XMT

lines. Refer to Fig. 2, in the 

Installation

 section.

Front Panel Test Jack Circuits

The four front panel test jacks provide internal connections for test

and calibration of the Term Set.

44443-01

This module includes the basic Term Set network circuits of the

44443-00, plus selectable strap connections for engaging an Idle

Line Termination (ILT) branch or Echo Suppression Override (ES)

branch across the 4-wire XMT port. Refer to Fig. 1.
The branch circuit selected in is controlled by relay K1. K1 is

energized by an external battery supply (-21 VDC to -56 VDC)

applied to pin 25 (-) and pin 29 (+). Relay K1 is protected from

excessive current flow by transistor Q1. Using Q1 to limit current

eliminates the need for a resistive voltage drop for -24 or -48 VDC

supplies.

Idle Line Termination Circuit

When K1 is energized, the normally closed side of K1A opens and

the 600 ohm ILT branch is disconnected. At the same time, the

normally open side of K1A closes, establishing the transmission

path to pin 49.
When K1 is released at the end of the call, the normally closed side

of K1A closes, reconnecting the 600 ohm termination across the 4-

wire XMT line. At the same time, the normally open side of K1A

re-opens, isolating the 600 ohm termination branch.

NOTE

: For the idle state to exist, the ILT bypass strap option should

not be used. Refer to Fig. 1

Echo Suppression Override Circuit

If K1 is energized, contact K1B is closed and connects a 50 ohm

load resistor across the 4-wire XMT line. This allows an override to

occur. If K1 is not energized, K1B remains open, disallowing an

override response.

NOTE

: Since the K1A (normally open) contact would normally open the

XMT line, the ILT bypass strap must be installed to prevent

interruption. Refer to Fig. 1

CIRCUIT DESCRIPTION

Summary of Contents for 44443

Page 1: ...Technical Reference TR NWT 000870 Copyright 1998 by Dantel Inc Dantel is a registered trademark of Dantel Inc ISO 9001 Registered Printed in the U S A INSTALLATION OPERATION MANUAL 44443 1098 90 00059...

Page 2: ...et applications The 44443 Term Set is a plug in printed circuit module that fits into any 400 type or similiar equipment housing The 44443 00 is a passive device which requires no supply voltage The 4...

Page 3: ...3 S3 1 S3 4 S3 5 S3 6 T GND T R J2 4W RCV 5 4 3 1 2 4 WIRE RECEIVE OUT 6 COM 1 IN 5 600 900 10 12 600 900 7 9 11 S1C S1A 8 T1 900 600 S2C 1 6 2 3 4 5 600 900 19 27 T2 900 600 S2A 600 900 S2B 7 9 11 12...

Page 4: ...The voice signal at the secondary of T2 is attenuated by a 600 ohm switchable pad and applied to pins 55 and 49 at the 4 wire XMT port Receive Mode In the receive mode a voice frequency entering pins...

Page 5: ...inates the need for a resistive voltage drop for 24 or 48 VDC supplies Idle Line Termination Circuit When K1 is energized the normally closed side of K1A opens and the 600 ohm ILT branch is disconnect...

Page 6: ...NEJACK PABX LINE STATION SELECTOR 49018 DTMF DECODER 44020 BUSY TONE GENERATOR J3 TIP RING REVERSED SWITCH DROP LINE Fig 2 shows a 44443 Term Set as part of a 00331 DTSS3ON Order Wire PABX Interface T...

Page 7: ...Strap Options Set the switches and straps using Fig 3 and Table A FIG 3 44443 TERM SET SWITCH AND STRAP LOCATIONS 44443 XX TERM SET A11 44443 00 RCV ATTEN dB OUT IN OUT IN 4 WIRE LINE XMT RCV 2 WIRE...

Page 8: ...to ILT ILT Bypass IN Load Strap to ES ILT Bypass IN Load Strap to OUT Wiring Normally the 44443 is used in a shelf that is pre wired at the factory Fig 4 shows the edge connector pin designations if...

Page 9: ...15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 CIRCUIT SIDE OF PC BOARD COMPONENT SIDE OF PC BOARD 4W XMT D Lead 4W XMT 2W R B Lead A Lead 2W T Ground ILT Relay Positive Input 01 only G Lead ILT Relay Negative...

Page 10: ...dBmO Measure minimum tone level Adjust S3 1 thru S3 6 for minimum level ACTION Remove Term Set and insert extender card in its place Insert Term Set into extender card When aligning 01 energize ILT r...

Page 11: ...cts to the output of the Term Set Echo Suppression Override Idle Line Termination Applications The 44443 01 features a relay activated echo suppression branch across the 4 wire XMT port This circuit i...

Page 12: ...cturer s authorized agent 5 When the installation of this device requires connection or changes to the internal wiring of registered telephones or other registered devices such changes and connections...

Page 13: ...Dissipation during relay operation 01 option only Physical Dimensions Weight 00 01 Operating Temperature Range VALUE 600 or 900 ohm in series with 2 15 uFd capacitor 600 ohm 5 4 5 dB nominal mid range...

Page 14: ...n instrument signed by a duly authorized officer of the Seller and accepted by the Buyer Warranty and remedies on products not manufactured by the Seller are in accordance with warranty of the respect...

Reviews: