Technical specifications
50-60 Hz data
Model
Nominal
tons 60Hz
Nominal cooling
capacity
Power
input
COP
E.E.R
Swept
volume Displacement Oil charge Net weight
TR
W
Btu/h
kW
W/W
Bty/h/W
cm3/rev
m3/h
dm3
kg
50Hz
WSH090
7.5
22400
76500
7.22
3.10
10.59
88.40
15.40
3.0
58.0
WSH105
9
26800
91500
8.60
3.12
10.63
103.50
18.00
3.3
64.0
WSH120
10
30200
103100
9.54
3.17
10.80
116.90
20.30
3.3
64.0
WSH140
12
34100
116400
10.70
3.19
10.87
133.00
23.12
3.3
67.0
WSH161
13
39000
133100
12.10
3.22
11.00
151.70
26.40
3.3
69.0
WSH184
15
44000
150200
13.65
3.22
11.00
170.30
29.60
3.6
71.5
60Hz
WSH090
7.5
27500
93900
8.62
3.19
10.88
88.40
18.60
3.0
58.0
WSH105
9
32700
111600
10.24
3.19
10.90
103.50
21.80
3.3
64.0
WSH120
10
37000
126300
11.38
3.25
11.08
116.90
24.60
3.3
64.0
WSH140
12
41600
142000
12.65
3.29
11.22
133.00
27.90
3.3
67.0
WSH161
13
47400
161800
14.40
3.29
11.22
151.70
31.90
3.3
69.0
WSH184
15
53100
181200
16.33
3.25
11.10
170.30
35.80
3.6
71.5
7
FRCC.PC.028.A5.02
Application Guidelines