4
T
h
ermosta
t Installa
tion
Installation
WP75-RF installation
Select a position for the WP75-RF that provides easy access to
the unit (it could be used on a daily basis by the user, so the
display needs to be clearly visible) and bearing in mind that
the maximum distance between the thermostat and sensor is
10 metres.
Prepare the fi xing position to provide access for the sensor
cable through the rear of the wallplate.
If the cable is to be surface fi xed note that it can only enter
the WP75-RF from the bottom through the positions shown
below.
Fix the wallplate so that the control module can be easily
attached or removed. Make the sensor wiring connections as
shown in the wiring diagram on page 7.
Before attaching the control module to the wallplate set the
DIL switch, located in a recess on the rear of the module, to
select whether the WP75-RF will be a 7 day controller or a 5/2
day (weekday/weekend) controller. Move both switches to
the desired position.
A
B
30mm min
Wall or plaster
box mounting
holes
Aperture for
rear entry
Clearance for
screwdriver access
Knockout for bottom
cable entry
Terminals
Outline of entry