Electrical data, connections and wiring
Fuses
Danfoss recommends using the fuses listed
below to protect service personnel and property
in case of component break-down in the
frequency converter.
For circuit breakers, Moeller types have been
tested and are recommended.
Frequency
converter
EN50178 compliant fuses
UL Compliant fuses
Recommended circuit breaker
Bussmann
SIBA
Little fuse
IP20
IP55
Size
Type
Type RK1
Type J
Type T
Type RK1
Type RK1
Moeller type
3x200-240V
CDS303-11kW
80A
gG
KTN-R80
JKS-80
JJN-80
5014006-080
KLN-R80
NZMB1-A100
NZMB1-A100
3x380-480V
CDS303-11kW
63A
gG
KTS-R40
JKS-40
JJS-40
5014006-040
KLS-R40
PKZM4-50
PKZM4-63
CDS303-15kW
63A
gG
KTS-R50
JKS-50
JJS-50
5014006-050
KLS-R50
PKZM4-50
PKZM4-63
3x525-600V
CDS303-15kW
63A
gG
KTS-R-45
JKS-45
JKJS-45
5014006-050
KLSR045
PKZM4-50
PKZM4-63
CDS303-22kW
63A
gG
KTS-R-60
JKS-60
JJS-60
5014006-063
KLSR060
NZMB1-A100
NZMB1-A100
From network to frequency converter
From frequency converter to compressor
Type
mm²
AWG
Type
mm²
AWG
200 - 240 V
CDS303-11kW
10
8
VZH052-J
10
8
CDS303-11kW
16
6
VZH065-J
16
6
380 - 400 V
CDS303-11kW
4
12
VZH052-G
4
12
CDS303-15kW
4
12
VZH065-G
6
10
525 - 600 V
CDS303-15kW
4
12
VZH052-H
4
12
CDS303-22kW
4
12
VZH065-H
6
10
Note: The wire size in the guideline is the maximum wire size that connectors can accept but not the actual needed cable. The need-
ed cable size should be specified by the OEM depending on the unit design, ambient temperature, the wire material, current, etc...
Wire sizes
Below table lists maximum wiring sizes for the motor compressor power supply cables.
from network
to drive
from drive to
to compressor
Circuit breaker
Power input
I
PR
ODUC
T INFORMA
TION
14