background image

7.3 Troubleshooting HE

Problem

Possible cause

Solution

Too little or no heat.

Strainer clogged in DH or HE circuit
(radiator circuit).

Clean gate/strainer(s).

The filter in the energy meter on DH circuit
clogged.

Clean the filter (after consulting the DH
plant operator).

Defective or wrongly adjusted differential
pressure controller.

Check the operation of the differential
pressure controller – clean the valve seat if
required.

Sensor defective – or possibly dirt in the
valve housing.

Check the operation of the thermostat –
clean the valve seat if required.

Automatic controls, if any, wrongly set or
defective - possibly power failure.

Check if the setting of the controller
is correct – see separate instructions.
Check the power supply. Temporary
setting of motor to “manual” control – see
instructions on automatic controls.

Pump out of operation.

Check if the pump is receiving power and
that it turns. Check if there is air trapped in
the pump housing – see pump manual.

The pump is set at too low speed of
rotation.

Set the pump at higher speed of rotation.

Pressure drop – the pressure drop on
the radiator circuit shows lower than
recommended operating pressure.

Fill water on the system and check the
functioning of the pressure expansion
vessel if required.

Air pockets in the system.

Vent the installation thoroughly.

Limiting of the return temperature adjusted
too low.

Adjust according to instructions.

Defective radiator valves.

Check – replace.

Uneven heat distribution in building
because of incorrectly set balancing valves,
or because there are no balancing valves.

Adjust/install balancing valves.

Diameter of pipe to substation too small or
branch pipe too long.

Check pipe dimensions.

Uneven heat distribution.

Air pockets in the system.

Vent the installation thoroughly.

DH supply temperature too high.

Wrong setting of thermostat or of
automatic controls, if any.

Adjust automatic controls, – see
instructions for automatic controls.

Defective controller. The controller does
not react as it should according to the
instructions.

Call automatic controls manufacturer or
replace the regulator.

Defective sensor on self-acting thermostat.

Replace thermostat – or sensor only.

DH supply temperature too low.

Wrong setting of automatic controls, if any.

Adjust automatic controls – see instructions
for automatic controls.

Defective controller. The controller does
not react as it should according to the
instructions.

Call in automatic controls manufacturer or
replace controller.

Defective sensor on self-acting thermostat.

Replace thermostat – or sensor only.

Wrong placement/fitting of outdoor
temperature sensor.

Adjust location of outdoor temperature
sensor.

Strainer clogged.

Clean gate/strainer.

24 | © Danfoss | 2023.10

AQ082486478026en-010501/ LUK4044301

Operating Guide Termix VVX-I with complete insulation

Summary of Contents for VVX-I

Page 1: ...Electrical connections 9 5 0 Design 10 5 1 Design 10 5 2 Schematic diagram 11 6 0 Controls 12 6 1 Heating circuit 12 6 2 DHW temperature control 17 6 3 Other 18 6 4 Extras 20 6 5 Maintenance 21 7 0 Tr...

Page 2: ...perature sensor Depending on the application different heat exchangers dimensioned for central or floor heating will be used Domestic hot water DHW The domestic hot water is prepared in the heat excha...

Page 3: ...personnel and call for expert help immediately REACH All Danfoss A S products fulfill the requirements in REACH One of the obligations in REACH is to inform customers about presence of Candidate list...

Page 4: ...g DH supply 2 District heating DH return 3 Heating HE supply 4 Heating HE return 5 Domestic hot water DHW 6 Domestic cold water DCW Connection sizes DH HE G int thread DCW DHW G int thread Dimensions...

Page 5: ...during transport all substation connections must be checked and tightened before installation Unused connections Unused connections and shut off valves must be sealed with a plug Should the plugs requ...

Page 6: ...ts of the bracket for the energy display and screw the two plugs supplied into the insulation front Mount the bracket for the display of the energy meter Mount the display calculator of the energy met...

Page 7: ...Start up 1 Pump speed Set the pump to highest speed before start up 2 Start pump Start the pump and heat through the system 3 Open shut off valves The shut off valves should then be opened and the un...

Page 8: ...at risk of seizure and any remaining warranty will be withdrawn Summer operation Switch off pump In summer the circulation pump must be switched off and the shut off valve to HE supply closed Running...

Page 9: ...or sensor must be connected to the station on the terminal block under the electronic control Authorized electrician Electrical connections must be made by an authorized electrician only Local standar...

Page 10: ...er DHW 14 Sensor pocket energy meter 41 Fitting piece energy meter 1 Summer valve 20 Filling drain valve 48 Air vent manual 4 Safety valve 26 Pressure gauge HE 63 Sieve 7 Thermostatic controller HE 31...

Page 11: ...Pressure gauge 63 Sieve 9 Strainer 31 Differential pressure controller 74 IHPT controller 10 Circulator pump DHW Domestic Hot Water DCW Domestic Cold Water DH Supply District Heating Supply DH Return...

Page 12: ...mperature controller 6 1 3 RAVK controller RAVK controller 25 65 C The temperature setting is as follows 1 25 C 2 35 C 3 45 C 4 55 C 5 65 C The values are intended as a guide Thermostatic control The...

Page 13: ...mostats it is recommended that thermostats be set for minimum temperature in each room 6 1 5 Outside temperature sensor Outdoor sensors should be mounted so as to avoid exposure to direct sunlight The...

Page 14: ...pressure proportional pressure or constant speed mode defined by the means of a smart user interface The variable speed modulating modes allow the pump to match its performance to the system requireme...

Page 15: ...Constant pressure Auto adapt Proportional pressure 1 Proportional pressure 2 2 pipe systems Proportional pressure 3 MAX Constant pressure 1 1 pipe systems Constant pressure 2 Under floor heating Const...

Page 16: ...6 1 9 HE pressure gauge The HE pressure gauge indicates the pressure of the HE system 16 Danfoss 2023 10 AQ082486478026en 010501 LUK4044301 Operating Guide Termix VVX I with complete insulation...

Page 17: ...compensated temperature controller with integrated differential pressure controller The IHPT operates at its best at DH supply temperatures of up to 100 C By turning the handle for temperature settin...

Page 18: ...3 2 Strainer Strainers should be cleaned regularly by authorized personnel The frequency of cleaning would depend on operating conditions and the manufacturer s instructions 6 3 3 GTU Pressure Equali...

Page 19: ...n the fitting piece 3 Remove fitting piece Remove the fitting piece and replace it with the energy meter Do not forget the gaskets 4 Tighten connections After mounting of the energy meter remember to...

Page 20: ...and fitting When mounting the hot water circulation directly on the controller the hot water circulation temperature will be equal to the idle temperature The idle temperature is a few degrees lower t...

Page 21: ...erature and DHW temperature Connections Checking all connections for leakages Safety valves The operation of the safety valves should be checked by turning the valve head in the indicated direction Ve...

Page 22: ...is at the normal level summer at least 60 C winter at least 70 C the differential pressure is equal to or higher than the normal local differential pressure in the DH network if in doubt ask the DH pl...

Page 23: ...ed with the DHW e g in a defective thermostatic mixing valve Check replace Hot water in some taps but not in all Defective or clogged non return valve on circulation valve Replace clean Tap temperatur...

Page 24: ...tion thoroughly Limiting of the return temperature adjusted too low Adjust according to instructions Defective radiator valves Check replace Uneven heat distribution in building because of incorrectly...

Page 25: ...he system should feature electronic controls as well as return sensors Pump pressure too high Adjust pump to a lower level Air in system Vent the system Defective or incorrectly set radiator valve s S...

Page 26: ...r to the applicable take back scheme for the recycling of electrical and electronic equipment Dispose of the product through channels provided for this purpose Comply with all local and currently appl...

Page 27: ...8 0 Declaration 8 1 Declaration of conformity AQ082486478026en 010501 LUK4044301 Danfoss 2023 10 27 Operating Guide Termix VVX I with complete insulation...

Page 28: ...28 Danfoss 2023 10 AQ082486478026en 010501 LUK4044301 Operating Guide Termix VVX I with complete insulation...

Reviews: