26-35 Term. X42/5 High Ref./Feedb. Value
Range:
Function:
100.000
*
[-999999.999 -
999999.999 ]
Enter the analog input scaling
value that corresponds to the
high voltage value set in
26-21 Terminal X42/3 High
Voltage
26-36 Term. X42/5 Filter Time Constant
Range:
Function:
0.001 s
*
[0.001 -
10.000 s]
Enter the time constant. This is a first-order
digital low pass filter time constant for
suppressing noise in terminal X42/5. A high
time constant value improves dampening
but also increases the time delay through
the filter. This parameter cannot be
adjusted while the motor is running.
26-37 Term. X42/5 Live Zero
Option:
Function:
This parameter makes it possible to enable the Live
Zero monitoring. E.g. where the analog input is a
part of the frequency converter control, rather than
being used as part of a decentral I/O system, such
as a Building Management System.
[0]
Disabled
[1]
*
Enabled
3.24.5 26-4* Analog Out X42/7
Parameters for configuring the scaling and output function
for analog output, terminal X42/7.
26-40 Terminal X42/7 Output
Option:
Function:
Set the function of terminal X42/7 as an
analog voltage output.
[0]
*
No operation
[100] Output freq.
0-100
: 0 - 100 Hz, (0-20 mA)
[101] Reference Min-
Max
: Minimum reference - Maximum
reference, (0-20 mA)
[102] Feedback
+-200%
: -200% to +200% of
, (0-20 mA)
[103] Motor cur. 0-Imax : 0 - Inverter Max. Current (
), (0-20 mA)
[104] Torque 0-Tlim
: 0 - Torque limit (
), (0-20 mA)
[105] Torque 0-Tnom
: 0 - Motor rated torque, (0-20 mA)
[106] Power 0-Pnom
: 0 - Motor rated power, (0-20 mA)
26-40 Terminal X42/7 Output
Option:
Function:
[107] Speed 0-HighLim : 0 - Speed High Limit (
and
), (0-20 mA)
[113] Ext. Closed Loop
1
: 0 - 100%, (0-20 mA)
[114] Ext. Closed Loop
2
: 0 - 100%, (0-20 mA)
[115] Ext. Closed Loop
3
: 0 - 100%, (0-20 mA)
[139] Bus ctrl.
: 0 - 100%, (0-20 mA)
[141] Bus ctrl t.o.
: 0 - 100%, (0-20 mA)
26-41 Terminal X42/7 Min. Scale
Range:
Function:
0.00
%
*
[0.00 -
200.00 %]
Scale the minimum output of the selected
analog signal at terminal X42/7, as a
percentage of the maximum signal level. E.g.
if a 0 V (or 0 Hz) is desired at 25% of the
maximum output value. Then programme
25%. Scaling values up to 100% can never be
higher than the corresponding setting in
26-42 Terminal X42/7 Max. Scale
.
See principle graph for
.
26-42 Terminal X42/7 Max. Scale
Range:
Function:
100.00
%
*
[0.00 -
200.00
%]
Scale the maximum output of the selected analog
signal at terminal X42/7. Set the value to the
maximum value of the voltage signal output.
Scale the output to give a voltage lower than 10V
at full scale; or 10V at an output below 100% of
the maximum signal value. If 10V is the desired
output current at a value between 0-100% of the
full-scale output, programme the percentage
value in the parameter, i.e. 50% = 10V. If a voltage
between 0 and 10V is desired at maximum
output, calculate the percentage as follows:
(
10
V
desired maximum voltage
)
x 100 %
i.e.
5
V : 10V
5
V × 100 % = 200 %
See principle graph for
6-52 Terminal 42 Output Max Scale
26-43 Terminal X42/7 Bus Control
Range:
Function:
0.00 %
*
[0.00 - 100.00 %] Holds the level of terminal X42/7 if
controlled by bus.
Parameter Description
VLT
®
HVAC Drive Programming Guide
MG.11.CB.02 - VLT
®
is a registered Danfoss trademark
181
3
3