3 Technical Data

3.1 Cabling Requirements

Choose suitable media for Ethernet data transmission. CAT5e and CAT6 cables are recommended for industrial applications. Both

types are available as unshielded twisted pair and shielded twisted pair.

Shielded cables are recommended for use in industrial environments and with drives.

A maximum cable length of 100 m (328 ft) is allowed between the switches.

3.2 Cable Specifications

PROFINET cables used are based electrically on category 5 balanced LAN cables according to ISO/IEC 11801 Edition 2.0, Class D.

Type C cables can be used in special applications (for example, the use of trailing cables and frequently moved machine parts), even
though their design and mechanical parameters can deviate from the specifications of type A and type B cables. Still, most of the
electrical parameters (for example, impedance levels) are retained.

Highly flexible copper cables generally have the finest stranded conductors and a highly resistant polyurethane outer sheath. Various
outer sheath materials are permitted to meet the various demands regarding resistance of industrial environments and exterior/
underground laying (natural and synthetic oil, grease, coolants/lubricants, chemicals, high and low temperatures, UV radiation, and so
on).

Table 2: Cable Specifications for Application Types A, B and C

Cable type

Application type A

Application type B

Application type C

Design

Data cable

Data cable

Data cable

Cable installation type

Stationary, no movement after
installation.

Flexible, occasional movement
or vibration.

Special applications (for example,
highly flexible, permanent move-
ment, vibration, or torsion).

Cable marking

PROFINET type A

PROFINET type B

PROFINET type C

Core cross-section

AWG 22/1

AWG 22/7

AWG 22/..

Outer diameter

5.5–8.0 mm (0.22–0.31 in)

Application dependent

Core diameter

1.5 ± 0.1 mm (0.06 ± 0.004 in)

Application dependent

Color (outer sheath)

Green RAL6018

Application dependent

Core identification (col-
ors)

star quad 2 pair

White, yellow, blue, orange

Pair 1: white (RXD+), blue (RXD-) Pair 2: yellow (TXD+), orange (TXT-)

Number of cores

4

Cable design

2 pairs or 1 star quad

Shielding design type

Aluminum foil + Cu braiding

Application

Plug type

RJ 45 (IP20 or IP65/67)/M12

Table 3: Transmission Performance Requirements

Relevant standard

ISO/IEC 11801 Edition 2.0, IEC 61156 (minimum Category 5)

Technical Data

Installation Guide  | VLT® PROFINET MCA 120

AN274237376992en-000101 / 130R0856 | 3

Danfoss A/S © 2019.03

Summary of Contents for VLT PROFINET MCA 120

Page 1: ...omationDrive FC 361 The installation guide is intended for use by qualified personnel Users are assumed to be familiar with the VLT drive with PROFINET technology and with the PC or PLC used as a mast...

Page 2: ...pe motors and remote DC link supplies including battery back ups UPS and DC link connections to other drives Wait for the capacitors to discharge fully The minimum waiting time is specified in table D...

Page 3: ...ments and exterior underground laying natural and synthetic oil grease coolants lubricants chemicals high and low temperatures UV radiation and so on Table 2 Cable Specifications for Application Types...

Page 4: ...Delay skew 20 ns 100 m Transfer impedance 50 m m at 10 MHz Technical Data Installation Guide VLT PROFINET MCA 120 AN274237376992en 000101 130R0856 4 Danfoss A S 2019 03...

Page 5: ...1 1 Illustration 1 PROFINET Connectors Table 4 PROFINET Connectors Signal M12 PIN RJ 45 RX 1 1 TX 2 2 RX 3 3 TX 4 4 8 Set the address switches if needed 9 Fit the LCP cradle 10 Fit the LCP or blind co...

Page 6: ...st Names Setting Switch 8 7 6 5 4 3 2 1 12 08 Host Name 128 64 32 16 8 4 2 1 005 OFF OFF OFF OFF OFF ON OFF ON 035 OFF OFF ON OFF OFF OFF ON ON 082 OFF ON OFF ON OFF OFF ON OFF 212 ON ON OFF ON OFF ON...

Page 7: ...ustration 3 Wiring 2 Fix the cable to the metal base plate using the springs 3 Tie down the cable and route it with other control wires inside the unit NOTICE Do not strip the Ethernet cable Ground th...

Page 8: ...erations can be made without subsequential changes being necessary in specifications already agreed All trademarks in this material are property of the respective companies Danfoss and the Danfoss log...

Reviews: