130BE232.10
Illustration 4.6 Mains, Motor, and Grounding Connection for
Single-phase Units
130BE231.10
Illustration 4.7 Mains, Motor, and Grounding Connection for 3-
phase Units
4.7 AC Mains Connection
4.7.1 AC Mains Connection
•
Size the wiring based on the input current of the
frequency converter. For maximum wire sizes, see
•
Comply with local and national electrical codes
for cable sizes.
Procedure
1.
Connect the AC input power cables to terminals
N and L for single-phase units (see
), or to terminals L1, L2, and L3 for
3-phase units (see
2.
Depending on the configuration of the
equipment, connect the input power to the
mains input terminals or the input disconnect.
3.
Ground the cable in accordance with the
grounding instructions in
4.
When supplied from an isolated mains source (IT
mains or floating delta) or TT/TN-S mains with a
grounded leg (grounded delta), ensure that the
RFI filter screw is removed, to avoid damage to
the intermediate circuit and reduce ground
capacity currents in accordance with IEC 61800-3.
Electrical Installation
Operating Instructions
MG07A102
Danfoss A/S © 11/2015 All rights reserved.
15
4
4