![Danfoss VLT Midi Drive FC 280 Operating Instructions Manual Download Page 49](http://html1.mh-extra.com/html/danfoss/vlt-midi-drive-fc-280/vlt-midi-drive-fc-280_operating-instructions-manual_3392296049.webp)
9 Specifications
9.1 Electrical Data
Frequency converter
typical shaft output [kW]
PK37
0.37
PK55
0.55
PK75
0.75
P1K1
1.1
P1K5
1.5
P2K2
2.2
P3K0
3
Enclosure IP20
K1
K1
K1
K1
K1
K1
K2
Output current
Shaft output [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
Continuous (3x380–440 V) [A]
1.2
1.7
2.2
3
3.7
5.3
7.2
Continuous (3x441–480 V) [A]
1.1
1.6
2.1
2.8
3.4
4.8
6.3
Intermittent (60 s overload) [A]
1.9
2.7
3.5
4.8
5.9
8.5
11.5
Continuous kVA (400 V AC) [kVA]
0.84
1.18
1.53
2.08
2.57
3.68
4.99
Continuous kVA (480 V AC) [kVA]
0.9
1.3
1.7
2.5
2.8
4.0
5.2
Maximum input current
Continuous (3x380–440 V) [A]
1.2
1.6
2.1
2.6
3.5
4.7
6.3
Continuous (3x441–480 V) [A]
1.0
1.2
1.8
2.0
2.9
3.9
4.3
Intermittent (60 s overload) [A]
1.9
2.6
3.4
4.2
5.6
7.5
10.1
More specifications
Maximum cable cross-section (mains, motor,
brake, and load sharing) [mm
2
(AWG)]
4(12)
Estimated power loss at rated maximum load
[W]
1)
20.88
25.16
30.01
40.01
52.91
73.97
94.81
Weight, enclosure IP20
2.3
2.3
2.3
2.3
2.3
2.5
3.6
Efficiency [%]
2)
96.2
97.0
97.2
97.4
97.4
97.6
97.5
Table 9.1 Mains Supply 3x380–480 V AC
Frequency converter
typical shaft output [kW]
P4K0
4
P5K5
5.5
P7K5
7.5
P11K
11
P15K
15
P18K
18.5
P22K
22
IP20
K2
K2
K3
K4
K4
K5
K5
Output current
Shaft output
4
5.5
7.5
11
15
18.5
22
Continuous (3x380–440 V) [A]
9
12
15.5
23
31
37
42.5
Continuous (3x441–480 V) [A]
8.2
11
14
21
27
34
40
Intermittent (60 s overload) [A]
14.4
19.2
24.8
34.5
46.5
55.5
63.8
Continuous kVA (400 V AC) [kVA]
6.24
8.32
10.74
15.94
21.48
25.64
29.45
Continuous kVA (480 V AC) [kVA]
6.8
9.1
11.6
17.5
22.4
28.3
33.3
Maximum input current
Continuous (3x380–440 V) [A]
8.3
11.2
15.1
22.1
29.9
35.2
41.5
Continuous (3x441–480 V) [A]
6.8
9.4
12.6
18.4
24.7
29.3
34.6
Intermittent (60 s overload) [A]
13.3
17.9
24.2
33.2
44.9
52.8
62.3
More specifications
Maximum cable size (mains, motor, brake)
[mm
2
(AWG)]
4(12)
16(6)
Estimated power loss at rated maximum load
[W]
1)
115.5
157.54
192.83
289.53
393.36
402.83
467.52
Weight enclosure IP20 [kg]
3.6
3.6
4.1
9.4
9.5
12.3
12.5
Efficiency [%]
2)
97.6
97.7
98.0
97.8
97.8
98.1
97.9
Table 9.2 Mains Supply 3x380–480 V AC
1) The typical power loss is at nominal load conditions and expected to be within
±
15% (tolerance relates to variety in voltage and
cable conditions).
Specifications
Operating Instructions
MG07A102
Danfoss A/S © 11/2015 All rights reserved.
47
9
9