Enclosure size
Power [kW] (hp)
CE compliance fuse
LVD circuit breaker
K1
0.37–2.2 (0.5–3)
gG-10
PKZM0-16
K2
3.0–5.5 (4–7.5)
gG-25
PKZM0-20
K3
7.5 (10)
gG-32
PKZM0-25
K4
11–15 (15–20)
gG-50
K5
18.5–22 (25–30)
gG-80
Table 9.4 CE Fuse, 380–480 V
9.9 Enclosure Sizes, Power Ratings and Dimensions
See
for the dimensions, and the top and bottom mounting holes.
Enclosure size
K1
K2
K3
K4
K5
Power Size
[kW (hp)]
Single-phase
200–240 V
0.37
(0.5)
0.55
(0.75)
0.75
(1.0)
1.1
(1.5)
1.5 (2.0)
2.2 (3.0)
–
–
–
3-phase
200–240 V
0.37
(0.5)
0.55
(0.75)
0.75
(1.0)
1.1
(1.5)
1.5 (2.0)
2.2 (3.0)
3.7 (5)
–
–
3-phase
380–480 V
0.37
(0.5)
0.55
(0.75)
0.75
(1.0)
1.1
(1.5)
1.5
(2.0)
2.2
(3.0)
3
(4)
4 (5)
5.5
(7.5)
7.5 (10)
11
(15)
15
(20)
18.5
(25)
22
(30)
Dimensions
[mm] (in)
Height A
210 (8.27)
272.5 (10.73)
272.5
(10.73)
317.5
(12.5)
410 (16.14)
Width B
75 (2.95)
90 (3.54)
115
(4.53)
133 (5.24)
150 (5.91)
Depth C
168 (6.61)
168 (6.61)
168
(6.61)
245 (9.65)
245 (9.65)
Mounting
holes
a
198 (7.8)
260 (10.24)
260
(10.24)
297.5
(11.71)
390 (15.35)
b
60 (2.36)
70 (2.76)
90 (3.54) 105 (4.13)
120 (4.72)
c
5 (0.2)
6.4 (0.25)
6.5
(0.26)
8 (0.315)
7.8 (0.307)
d
9 (0.35)
11 (0.43)
11 (0.43)
12.4
(0.488)
12.6 (0.496)
e
4.5 (0.177)
5.5 (0.22)
5.5
(0.22)
6.8 (0.27)
7 (0.28)
f
7.3 (0.287)
8.1 (0.319)
9.2
(0.362)
11 (0.43)
11.2 (0.44)
Table 9.5 Enclosure Sizes, Power Ratings and Dimensions
Specifications
Instruction Manual
MG07A122
Danfoss A/S © 11/2015 All rights reserved.
55