Danfoss VLT Micro Drive Quick Manual Download Page 5

1.3.5 Fuses

Branch circuit protection:
In order to protect the installation against electrical and
fire hazard, all branch circuits in an installation, switch
gear, machines etc., must be short-circuited and
overcurrent protected according to national/international
regulations.

Short circuit protection:
Danfoss recommends using the fuses mentioned in the
following tables to protect service personnel or other
equipment in case of an internal failure in the unit or
short-circuit on DC-link. The frequency converter provides
full short circuit protection in case of a short-circuit on the
motor or brake output.

Overcurrent protection:
Provide overload protection to avoid overheating of the
cables in the installation. Overcurrent protection must
always be carried out according to national regulations.
Fuses must be designed for protection in a circuit capable
of supplying a maximum of 100,000A

rms

 (symmetrical),

480V maximum.

Non UL compliance:
If UL/cUL is not to be complied with, Danfoss recommends
using the fuses mentioned in the below table, which will
ensure compliance with EN50178/IEC61800-5-1:
In case of malfunction, not following the fuse recommen-
dation may result in damage to the frequency converter.

FC 51

Max. Fuses UL

Max. fuses non UL

Bussmann

Bussmann

Bussmann

Littel fuse

Ferraz-

Shawmut

Ferraz-

Shawmut

1 X 200-240V
kW

Type RK1

Type J

Type T

Type RK1

Type CC

Type RK1

Type gG

0K18 - 0K37

KTN-R15

JKS-15

JJN-15

KLN-R15

ATM-R15

A2K-15R

16A

0K75

KTN-R25

JKS-25

JJN-25

KLN-R25

ATM-R25

A2K-25R

25A

1K5

KTN-R35

JKS-35

JJN-35

KLN-R35

-

A2K-35R

35A

2K2

KTN-R50

JKS-50

JJN-50

KLN-R50

-

A2K-50R

50A

3 x 200-240V
0K25

KTN-R10

JKS-10

JJN-10

KLN-R10

ATM-R10

A2K-10R

10A

0K37

KTN-R15

JKS-15

JJN-15

KLN-R15

ATM-R15

A2K-15R

16A

0K75

KTN-R20

JKS-20

JJN-20

KLN-R20

ATM-R20

A2K-20R

20A

1K5

KTN-R25

JKS-25

JJN-25

KLN-R25

ATM-R25

A2K-25R

25A

2K2

KTN-R40

JKS-40

JJN-40

KLN-R40

ATM-R40

A2K-40R

40A

3K7

KTN-R40

JKS-40

JJN-40

KLN-R40

-

A2K-40R

40A

3 x 380-480V
0K37 - 0K75

KTS-R10

JKS-10

JJS-10

KLS-R10

ATM-R10

A6K-10R

10A

1K5

KTS-R15

JKS-15

JJS-15

KLS-R15

ATM-R15

A2K-15R

16A

2K2

KTS-R20

JKS-20

JJS-20

KLS-R20

ATM-R20

A6K-20R

20A

3K0

KTS-R40

JKS-40

JJS-40

KLS-R40

ATM-R40

A6K405R

40A

4K0

KTS-R40

JKS-40

JJS-40

KLS-R40

ATM-R40

A6K-40R

40A

5K5

KTS-R40

JKS-40

JJS-40

KLS-R40

-

A6K-40R

40A

7K5

KTS-R40

JKS-40

JJS-40

KLS-R40

-

A6K-40R

40A

11K0

KTS-R60

JKS-60

JJS-60

KLS-R60

-

A6K-60R

63A

15K0

KTS-R60

JKS-60

JJS-60

KLS-R60

-

A6K-60R

63A

18K5

KTS-R60

JKS-60

JJS-60

KLS-R60

-

A6K-60R

80A

22K0

KTS-R60

JKS-60

JJS-60

KLS-R60

-

A6K-60R

80A

Table 1.3 Fuses

Quick Guide

VLT Micro Drive Quick Guide

4

MG.02.B6.02 - VLT

®

 is a registered Danfoss trademark

1

1

Summary of Contents for VLT Micro Drive

Page 1: ...MAKING MODERN LIVING POSSIBLE Quick Guide VLT Micro Drive...

Page 2: ...equency switching at high power This will generate a leakage current in the earth connection A fault current in the frequency converter at the output power terminals might contain a DC component which...

Page 3: ...e the frequency converter is connected to mains the motor can be started stopped using digital commands bus commands references or via the LCP Disconnect the frequency converter from mains whenever pe...

Page 4: ...248 9 5 1 For LCP with potentiometer please add 7 6mm Table 1 1 Mechanical Dimensions 1 3 4 Electrical Installation in General NOTE All cabling must comply with national and local regulations on cable...

Page 5: ...FC 51 Max Fuses UL Max fuses non UL Bussmann Bussmann Bussmann Littel fuse Ferraz Shawmut Ferraz Shawmut 1 X 200 240V kW Type RK1 Type J Type T Type RK1 Type CC Type RK1 Type gG 0K18 0K37 KTN R15 JKS...

Page 6: ...and W Step 3 Mount mains supply to terminals L1 L L2 and L3 N 3 phase or L1 L and L3 N single phase and tighten Illustration 1 2 Mounting of Earth Cable Mains and Motor Wires 1 3 7 Control Terminals...

Page 7: ...lying Start term 18 and an analog reference term 53 or 60 make the frequency converter run Illustration 1 5 Overview of Control Terminals in PNP configuration and Factory Setting Quick Guide VLT Micro...

Page 8: ...3 9 Load sharing Brake Use 6 3 mm insulated Faston Plugs designed for high voltage for DC Load Sharing and brake Contact Danfoss or see instruction no MI 50 Nx 02 for load sharing and instruction no...

Page 9: ...C via RS485 com port by installing the MCT 10 Set up Software This software can either be ordered using code number 130B1000 or downloaded from the Danfoss Web site www danfoss com BusinessAreas Drive...

Page 10: ...above the operation keys indicates the active key Hand on Starts the motor and enables control of the frequency converter via the LCP Off Reset Stops the motor off If in alarm mode the alarm will be r...

Page 11: ...oast delay time 1 73 Flying Start 0 Disabled 1 Enabled 1 8X Stop Adjustments 1 80 Function at Stop 0 Coast 1 DC hold 1 82 Min Speed for Funct at Stop Hz 0 0 20 0 Hz 0 0 Hz 1 9XMotor Temperature 1 90 M...

Page 12: ...minal 60 Filter Time Constant 0 01 10 00s 0 01s 6 8X LCP potentiometer 6 80 LCP Potmeter Enable 0 Disabled 1 Enable 6 81 LCP potm Low Reference 4999 4999 0 000 6 82 LCP potm High Reference 4999 4999 5...

Page 13: ...4 01 Switching Frequency 0 2 kHz 1 4 kHz 2 8 kHz 4 16 kHz not available for M5 14 03 Overmodulation 0 Off 1 On 14 1X Mains monitoring 14 12 Function at mains imbalance 0 Trip 1 Warning 2 Disabled 14 2...

Page 14: ...h fault X X Discharge from output phases to ground 47 Control Voltage Fault X X 24 V DC may be overloaded 51 AMT check Unom and Inom X Wrong setting for motor voltage and or motor current 52 AMT low I...

Page 15: ...C 1 At rated load conditions 1 7 2 Mains Supply 3 x 200 240V AC Normal overload 150 for 1 minute Frequency converter Typical Shaft Output kW PK25 0 25 PK37 0 37 PK75 0 75 P1K5 1 5 P2K2 2 2 P3K7 3 7 Ty...

Page 16: ...Supply 3 x 380 480V AC 1 At rated load conditions Normal overload 150 for 1 minute Frequency converter Typical Shaft Output kW P5K5 5 5 P7K5 7 5 P11K 11 P15K 15 P18K 18 5 P22K 22 Typical Shaft Output...

Page 17: ...ing not more than 100 000 RMS symmetrical Amperes 240 480V maximum Motor output U V W Output voltage 0 100 of supply voltage Output frequency 0 200Hz VVC 0 400Hz u f Switching on output Unlimited Ramp...

Page 18: ...mable relay output 1 Relay 01 Terminal number 01 03 break 01 02 make Max terminal load AC 1 1 on 01 02 NO Resistive load 250V AC 2 A Max terminal load AC 15 1 on 01 02 NO Inductive load cos 0 4 250V A...

Page 19: ...C Minimum ambient temperature at reduced performance 10 C Temperature during storage transport 25 65 70 C Maximum altitude above sea level without derating 1000 m Maximum altitude above sea level with...

Page 20: ...he motor is adequate A problem may occur at low speeds in constant torque applications Running continuously at low speeds below half the nominal motor speed may require additional air cooling Alternat...