Danfoss VLT Micro Drive Quick Manual Download Page 11

1.5  Parameter Overview

Parameter Overwiev

0-XX Operation/Display

0-0X Basic Settings

0-03 Regional Settings

*[0] International

[1] US

0-04 Oper. State at Power-up

(Hand)

[0] Resume

*[1] Forced stop, ref = old

[2] Forced stop, ref = 0

0-1X Set-up Handling

0-10 Active Set-up

*[1] Setup 1

[2] Setup 2

[9] Multi Setup

0-11 Edit Set-up

*[1] Setup 1

[2] Setup 2

[9] Active Setup

0-12 Link Setups

[0] Not Linked

*[20] Linked

0-31 Custom Readout Min Scale

0.00 – 9999.00 * 0.00

0-32 Custom Readout Max Scale

0.00 – 9999.00 * 100.0

0-4X LCP Keypad

0-40 [Hand on] Key on LCP

[0] Disabled

*[1] Enabled

0-41 [Off / Reset] Key on LCP

[0] Disable All

*[1] Enable All

[2] Enable Reset Only

0-42 [Auto on] Key on LCP

[0] Disabled

*[1] Enabled

0-5X Copy/Save

0-50 LCP Copy

*[0] No copy

[1] All to LCP

[2] All from LCP

[3] Size indep. from LCP

0-51 Set-up Copy

*[0] No copy

[1] Copy from setup 1

[2] Copy from setup 2

[9] Copy from Factory setup

0-6X Password

0-60 (Main) Menu Password

0-999 *0

0-61 Access to Main/Quick Menu

w/o Password

*[0] Full access

[1] LCP:Read Only

[2] LCP:No Access

1-XX Load/Motor

1-0X General Settings

1-00 Configuration Mode

*[0] Speed open loop

[3] Process

1-01 Motor Control Principle

[0] U/f

*[1] VVC+

1-03 Torque Characteristics

*[0] Constant torque

[2] Automatic Energy Optim.

1-05 Local Mode Configuration

[0] Speed Open Loop

*[2] As config in par. 1-00

1-2X Motor Data

1-20 Motor Power [kW] [HP]

[1] 0.09kW/0.12HP

[2] 0.12kW/0.16HP

[3] 0.18kW/0.25HP

[4] 0.25kW/0.33HP

[5] 0.37kW/0.50HP

[6] 0.55kW/0.75HP

[7] 0.75kW/1.00HP

[8] 1.10kW/1.50HP

[9] 1.50kW/2.00HP

[10] 2.20kW/3.00HP

[11] 3.00kW/4.00HP

[12] 3.70kW/5.00HP

[13] 4.00kW/5.40HP

[14] 5.50kW/7.50HP

[15] 7.50kW/10.00HP

[16] 11.00kW/15.00HP

[17] 15.00kW/20.00HP

[18] 18.50kW/25.00HP

[19] 22.00kW/29.50HP

[20] 30.00kW/40.00HP

1-22 Motor Voltage

50 - 999V * 230 - 400V

1-23 Motor Frequency

20 - 400Hz * 50Hz

1-24 Motor Current

0.01 - 100.00A * Motortype dep.

1-25 Motor Nominal Speed

100 - 9999rpm * Motortype dep.

1-29 Automatic Motor Tuning

(AMT)

*[0] Off

[2] Enable AMT

1-3X Adv. Motor Data

1-30 Stator Resistance (Rs)

[Ohm] * Dep. on motor data

1-33 Stator Leakage Reactance (X1)

[Ohm] * Dep. on motor data

1-35 Main Reactance (Xh)

[Ohm] * Dep. on motor data

1-5X Load Indep. Setting

1-50 Motor Magnetisation at 0

Speed

0 - 300 % * 100 %

1-52 Min Speed Norm. Magnet. [Hz]

0.0 - 10.0Hz * 0.0Hz

1-55 U/f Characteristic - U

0 - 999.9V

1-56 U/f Characteristic - F

0 - 400Hz

1-6X Load Depen. Setting

1-60 Low Speed Load Compen-

sation

0 - 199% * 100%

1-61 High Speed Load Compen-

sation

0 - 199% * 100%

1-62 Slip Compensation

-400 - 399% * 100%

1-63 Slip Compensation Time

Constant

0.05 - 5.00s * 0.10s

1-7X Start Adjustments

1-71 Start Delay

0.0 - 10.0s * 0.0s

1-72 Start Function

[0] DC hold / delay time

[1] DC brake / delay time

*[2] Coast / delay time

1-73 Flying Start

*[0] Disabled

[1] Enabled

1-8X Stop Adjustments

1-80 Function at Stop

*[0] Coast

[1] DC hold

1-82 Min Speed for Funct. at Stop

[Hz]

0.0 - 20.0 Hz * 0.0 Hz

1-9XMotor Temperature

1-90 Motor Thermal Protection

*[0] No protection

[1] Termistor warning

[2] Thermistor trip

[3] Etr warning

[4] Etr trip

1-93 Thermistor Resource

*[0] None

[1] Analog input 53

[6] Digital input 29

2-XX Brakes

2-0XDC-Brake

2-00 DC Hold Current

0 - 150% * 50%

2-01 DC Brake Current

0 - 150% * 50%

2-02 DC Braking Time

0.0 - 60.0s * 10.0s

2-04 DC Brake Cut In Speed

0.0 - 400.0Hz * 0.0Hz

2-1X Brake Energy Funct.

2-10 Brake Function

*[0] Off

[1] Resistor brake

[2] AC brake

2-11 Brake Resistor (ohm)

5 - 5000 * 5

2-16 AC Brake, Max current

0 - 150 % * 100%

2-17 Over-voltage Control

*[0] Disabled

[1] Enabled (not at stop)

[2] Enabled

2-2* Mechanical Brake

2-20 Release Brake Current

0.00 - 100.0A * 0.00A

2-22 Activate Brake Speed [Hz]

0.0 - 400.0Hz * 0.0Hz

3-XX Reference / Ramps

3-0X Reference Limits

3-00 Reference Range

*[0] Min - Max

[1] -Max - +Max

3-02 Minimum Reference

-4999 - 4999 * 0.000

3-03 Maximum Reference

-4999 - 4999 * 50.00

3-1X References

3-10 Preset Reference

-100.0 - 100.0% * 0.00%

3-11 Jog Speed [Hz]

0.0 - 400.0Hz * 5.0Hz

3-12 Catch up/slow Down Value

0.00 - 100.0% * 0.00%

3-14 Preset Relative Reference

-100.0 - 100.0 % * 0.00 % 3-15

Reference Resource 1

[0] No function

*[1] Analog Input 53

[2] Analog input 60

[8] Pulse input 33

[11] Local bus ref

[21] LCP Potentiometer

3-16 Reference Resource 2

[0] No function

[1] Analog Input 53

*[2] Analog input 60

[8] Pulse input 33

*[11] Local bus ref

[21] LCP Potentiometer

3-17 Reference Resource 3

[0] No function

[1] Analog Input 53

[2] Analog input 60

[8] Pulse input 33

*[11] Local bus ref

[21] LCP Potentiometer

3-18 Relative Scaling Ref. Resource

*[0] No function

[1] Analog Input 53

[2] Analog input 60

[8] Pulse input 33

[11] Local bus ref

[21] LCP Potentiometer

3-4X Ramp 1

3-40 Ramp 1 Type

*[0] Linear

[2] Sine2 ramp

3-41 Ramp 1 Ramp up Time
0.05 - 3600s * 3.00s (10.00s

1)

)

3-42 Ramp 1 Ramp Down Time
0.05 - 3600s * 3.00s (10.00s 

1)

)

3-5X Ramp 2

3-50 Ramp 2 Type

*[0] Linear

[2] Sine2 ramp

3-51 Ramp 2 Ramp up Time
0.05 - 3600s * 3.00s (10.00 s 

1)

)

3-52 Ramp 2 Ramp down Time
0.05 - 3600s * 3.00s (10.00 s

1)

)

3-8X Other Ramps

3-80 Jog Ramp Time
0.05 - 3600s * 3.00s (10.00s

1)

)

3-81 Quick Stop Ramp Time
0.05 - 3600s * 3.00s (10.00s

1)

)

4-XX Limits / Warnings

4-1X Motor Limits

4-10 Motor Speed Direction

[0] Clockwise

[1] CounterClockwise

*[2] Both

4-12 Motor Speed Low Limit [Hz]

0.0 - 400.0Hz * 0.0Hz

4-14 Motor Speed High Limit [Hz]

0.1 - 400.0 Hz * 65.0 Hz

4-16 Torque Limit Motor Mode

0 - 400 % * 150 %

4-17 Torque Limit Generator Mode

0 - 400% * 100%

4-5X Adj. Warnings

4-50 Warning Current Low

0.00 - 100.00A * 0.00A

4-51 Warning Current High

0.00 - 100.00A * 100.00A

4-58 Missing Motor Phase Function

[0] Off

*[1] On

1)

 M4 and M5 only

Quick Guide

VLT Micro Drive Quick Guide

10

MG.02.B6.02 - VLT

®

 is a registered Danfoss trademark

1

1

Summary of Contents for VLT Micro Drive

Page 1: ...MAKING MODERN LIVING POSSIBLE Quick Guide VLT Micro Drive...

Page 2: ...equency switching at high power This will generate a leakage current in the earth connection A fault current in the frequency converter at the output power terminals might contain a DC component which...

Page 3: ...e the frequency converter is connected to mains the motor can be started stopped using digital commands bus commands references or via the LCP Disconnect the frequency converter from mains whenever pe...

Page 4: ...248 9 5 1 For LCP with potentiometer please add 7 6mm Table 1 1 Mechanical Dimensions 1 3 4 Electrical Installation in General NOTE All cabling must comply with national and local regulations on cable...

Page 5: ...FC 51 Max Fuses UL Max fuses non UL Bussmann Bussmann Bussmann Littel fuse Ferraz Shawmut Ferraz Shawmut 1 X 200 240V kW Type RK1 Type J Type T Type RK1 Type CC Type RK1 Type gG 0K18 0K37 KTN R15 JKS...

Page 6: ...and W Step 3 Mount mains supply to terminals L1 L L2 and L3 N 3 phase or L1 L and L3 N single phase and tighten Illustration 1 2 Mounting of Earth Cable Mains and Motor Wires 1 3 7 Control Terminals...

Page 7: ...lying Start term 18 and an analog reference term 53 or 60 make the frequency converter run Illustration 1 5 Overview of Control Terminals in PNP configuration and Factory Setting Quick Guide VLT Micro...

Page 8: ...3 9 Load sharing Brake Use 6 3 mm insulated Faston Plugs designed for high voltage for DC Load Sharing and brake Contact Danfoss or see instruction no MI 50 Nx 02 for load sharing and instruction no...

Page 9: ...C via RS485 com port by installing the MCT 10 Set up Software This software can either be ordered using code number 130B1000 or downloaded from the Danfoss Web site www danfoss com BusinessAreas Drive...

Page 10: ...above the operation keys indicates the active key Hand on Starts the motor and enables control of the frequency converter via the LCP Off Reset Stops the motor off If in alarm mode the alarm will be r...

Page 11: ...oast delay time 1 73 Flying Start 0 Disabled 1 Enabled 1 8X Stop Adjustments 1 80 Function at Stop 0 Coast 1 DC hold 1 82 Min Speed for Funct at Stop Hz 0 0 20 0 Hz 0 0 Hz 1 9XMotor Temperature 1 90 M...

Page 12: ...minal 60 Filter Time Constant 0 01 10 00s 0 01s 6 8X LCP potentiometer 6 80 LCP Potmeter Enable 0 Disabled 1 Enable 6 81 LCP potm Low Reference 4999 4999 0 000 6 82 LCP potm High Reference 4999 4999 5...

Page 13: ...4 01 Switching Frequency 0 2 kHz 1 4 kHz 2 8 kHz 4 16 kHz not available for M5 14 03 Overmodulation 0 Off 1 On 14 1X Mains monitoring 14 12 Function at mains imbalance 0 Trip 1 Warning 2 Disabled 14 2...

Page 14: ...h fault X X Discharge from output phases to ground 47 Control Voltage Fault X X 24 V DC may be overloaded 51 AMT check Unom and Inom X Wrong setting for motor voltage and or motor current 52 AMT low I...

Page 15: ...C 1 At rated load conditions 1 7 2 Mains Supply 3 x 200 240V AC Normal overload 150 for 1 minute Frequency converter Typical Shaft Output kW PK25 0 25 PK37 0 37 PK75 0 75 P1K5 1 5 P2K2 2 2 P3K7 3 7 Ty...

Page 16: ...Supply 3 x 380 480V AC 1 At rated load conditions Normal overload 150 for 1 minute Frequency converter Typical Shaft Output kW P5K5 5 5 P7K5 7 5 P11K 11 P15K 15 P18K 18 5 P22K 22 Typical Shaft Output...

Page 17: ...ing not more than 100 000 RMS symmetrical Amperes 240 480V maximum Motor output U V W Output voltage 0 100 of supply voltage Output frequency 0 200Hz VVC 0 400Hz u f Switching on output Unlimited Ramp...

Page 18: ...mable relay output 1 Relay 01 Terminal number 01 03 break 01 02 make Max terminal load AC 1 1 on 01 02 NO Resistive load 250V AC 2 A Max terminal load AC 15 1 on 01 02 NO Inductive load cos 0 4 250V A...

Page 19: ...C Minimum ambient temperature at reduced performance 10 C Temperature during storage transport 25 65 70 C Maximum altitude above sea level without derating 1000 m Maximum altitude above sea level with...

Page 20: ...he motor is adequate A problem may occur at low speeds in constant torque applications Running continuously at low speeds below half the nominal motor speed may require additional air cooling Alternat...

Page 21: ...www danfoss com drives MG02B602 132R0029 MG02B602 Rev 2011 08 03...

Reviews: