3.5.5 Recommendation of Fuses
Table 4: Fuses
FC 51
Maximum fuses non–UL
kW
Type gG
1x200–240 V
0K18–0K37
16A
0K75
25A
1K5
35A
2K2
50A
3x380–480 V
0K37–0K75
10A
1K5
16A
2K2
20A
3K0
40A
4K0
40A
5K5
40A
7K5
40A
11K0
63A
15K0
63A
18K5
80A
22K0
80A
3.6 Connecting to Mains and Motor
The drive is designed to operate all standard 3-phased asynchronous motors.
The drive is designed to accept mains/ motor cables with a maximum cross-section of 4 mm
2
/10 AWG (M1, M2, and M3), and a
maximum cross-section of 16 mm
2
/6 AWG (M4 and M5).
AQ348848915086en-000101 / 130R0943 | 11