Table 50: 2-14 - Start Delay
Range
Function
* 0 s
0:00–60:00 (minutes:seconds)
Sets a delay after the soft starter receives a start command before it starts the motor.
Table 51: 2-15 - DC Brake Torque
Range
Function
* 20%
20–100%
Sets the amount of brake torque the soft starter uses to slow the motor.
Table 52: 2-16 - DC Brake Time
Range
Function
* 1 s
0:01–0:30 (minutes:seconds)
Sets the duration for DC injection during a braking stop.
Table 53: 2-17- Brake Current Limit
Range
Function
* 250%
100–600% FLC
Sets the current limit for soft brake.
Table 54: 2-18 - Soft Brake Delay
Range
Function
*400 ms 400–2000
ms
Sets the time which the soft starter waits after a stop signal is received before it begins to supply brak-
ing current to the motor. Set to allow time for K1 and K2 to switch.
10.7 Parameter Group 3-** Motor Start/Stop-2
The parameters in this group control the operation of the secondary configuration of the motor. Use the programmable input to
select the active motor set.
See
Table 55: 3-1 - Motor Full Load Current-2
Range
Function
Model dependent
Sets the secondary motor's full load current.
Table 56: 3-2 - Motor kW-2
Range
Function
* 0
0–9999 kW
Sets the running power of the secondary motor in kW.
Table 57: 3-3 - Start Mode-2
Option
Function
Selects the soft start mode.
*
Constant Current
Adaptive Control
Table 58: 3-4 - Start Ramp Time-2
Range
Function
*10 s 0:01–3:00 (minutes:sec-
onds)
Sets the total start time for an adaptive control start or the ramp time for current ramp starting
(from the initial current to the current limit).