Option
Function
Read Only
Prevents users altering parameter values in the Main Menu.
Parameter values can still be viewed.
Table 168: 10-8 - User Parameter 1
Option
Function
Selects which information is shown on the main monitoring screen.
Blank
Shows no data in the selected area, allowing long messages to be shown without overlapping.
* Current
Average rms current across all 3 phases.
Motor Voltage
Average rms voltage across all 3 phases.
P1 Voltage
Phase 1 voltage.
P2 Voltage
Phase 2 voltage.
P3 Voltage
Phase 3 voltage.
Mains Frequency
The average frequency measured on 3 phases.
Motor pf
The motor's power factor, measured by the soft starter.
Motor Power
The motor's running power in kW.
Motor Temp (%)
The motor's temperature, calculated by the thermal model.
Hours Run
The number of hours the motor has run via the soft starter.
Number of Starts
The number of starts the soft starter has completed since the start counter was last reset.
Pump Pressure
The pressure at the pump, as configured in
parameters 30-2
to
30-4
. This information is only availa-
ble if the smart card is installed.
Pump Flow
The flow at the pump, as configured in
parameters 30-6
to
30-11
. This information is only available if
the smart card is installed.
Well Depth
The depth of the well, as configured in
parameters 30-13
to
30-15
. This information is only available
if the smart card is installed.
Pump Temperature
The pump temperature, as measured by the PT100. This information is only available if the smart
card is installed.
Analog Output Value
The value of the analog output (see
parameter group 9-** Analog Output
).
Heat Sink Temperature The soft starter's temperature measured at the heat sink.
Bypass Model (%)
The percentage of thermal capacity remaining in the bypass contactor.
SCR Temperature
The temperature of the SCRs calculated by the thermal model.
Rating Capacity (%)
The thermal capacity available in the soft starter for its next start.
Table 169: 10-9 - User Parameter 2
Option
Function
Selects which information is shown on the main monitoring screen.
See
parameter 10-8 User Parameter 1
for details.
AQ262141844215en-000401 / 175R1174
108 | Danfoss A/S © 2020.12
Programmable Parameters
VLT® Soft Starter MCD 600
Operating Guide