5.2 On-board Web Server
5.2.1 Connect to the Device
To configure settings using the on-board web server, the device must be installed in a soft starter, control power must be available,
and the device and computer must both be connected to the Ethernet network.
The computer must use a fixed IP address (not DHCP) and the same subnet mask as the device. The default IP address for a new
PROFINET Module is 192.168.1.2. The default subnet mask is 255.255.255.0.
e7
7h
a8
07
.1
0
Once connected, the web server reports basic information about the device and the soft starter.