Closed Loop Set-up Wizard
No & Name
Range
Default
Function
[0] International
[1] US
0
0.09-110kW
Size related Enter motor power from nameplate data
50.0 - 1000.0V
Size related Enter motor voltage from nameplate data
20.0 - 400.0Hz
Size related Enter motor frequency from nameplate data
0.01 - 10000.00A
Size related Enter motor current from nameplate data
100.0 - 9999.0RPM
Size related Enter motor nominal speed from nameplate data
0.0 - 400Hz
0.0Hz
Enter the minimum limit for low speed
0 - 400Hz
65Hz
Enter the maximum limit for high speed
0.05 - 3600.0 s
Size related Ramp up time from 0 to rated motor frequency par. 1-23
0.05 - 3600.0 s
Size related Ramp down time from rated
to 0
[0] Disabled
[1] Enabled
0
Select Enable to enable the frequency converter to catch a
spinning motor
-4999-4999
0
The minimum reference is the lowest value obtainable by
summing all references
-4999-4999
50
The maximum reference is the highest value obtainable by
summing all references
-100-100%
0
Enter the set point
[0] Current
[1] Voltage
1
Select if terminal 53 is used for current- or voltage input
0-10V
0.07V
Enter the voltage that corresponds to the low reference value
0-10V
10V
Enter the voltage that corresponds to the low high reference
value
0-20mA
4
Enter the current that corresponds to the high reference value
0-20mA
20
Enter the current that corresponds to the high reference value
-4999-4999
0
Enter the feedback value that corresponds to the voltage or
current set in par. 6-10/6-12
-4999-4999
50
Enter the feedback value that corresponds to the voltage or
current set in par. 6-11/6-13
0-10 s
0.01
Enter the filter time comstant
[0] Normal
[1] Inverse
0
Select
Normal
[0] to set the process control to increase the output
speed when the process error is positive. Select
Inverse
[1] to
reduce the output speed.
0-200Hz
0
Enter the motor speed to be attained as a start signal for
commencement of PI control
0-10
0.01
Enter the process controller proportional gain. Quick control is
obtained at high amplification. However if amplification os too
great, the process may become unstable
See
Off
Performing an AMA optimizes motor performance
How to Programme
VLT HVAC Basic Drive Programming Guide