Parameter

Range

Default

Function

25-58 Run
Next Pump
Delay

0.1-5.0 s

*0.1 s

Time between
stopping the old
variable speed
pump and
starting the new
appointed pump.

25-59 Run on
Mains Delay

Expressionlimit
(0.1)-5.0 s

*0.5 s

Time delay
before a fixed
speed pump is
staged on
according to
normal staging
sequence.

25-80 Cascade
Status

 

 

View the control
status for the
Cascade
Controller.

25-81 Pump
Status

0-0

* 0

View the status
for the pumps
connected:
X=Disabled,
O=Off, D=Speed
controlled,
R=Mains.

Parameter

Range

Default

Function

25-84 Pump
ON Time

0-2147483647

* 0

View the total
operating hours
of the connected
pumps. Can be
reset by writing
0..

25-90 Pump
Interlock

*[0] Off
[1] On

*[0] Off

Choose the
pump to
interlock for e.g.
service. The
pump will be
taken out of any
pump cycling etc.

Table 1.3

1.2  Installation

1.2.1 Control Terminals

Illustration 1.3

 shows all control terminals of the frequency

converter. Applying Start (terminal 18), connection
between terminal 12-27 and an analog reference (terminal
53 or 54 and 55) make the frequency converter run.

18 19

12   20  55

27 29 42 45 50 53 54

DIGI IN/OUT

DIGI IN/OUT

DIGI IN

DIGI IN

61 68 69

N

P

COMM. GND

+24V

0/4-20mA A OUT / DIG OUT

0/4-20mA A OUT / DIG OUT

COM A IN

COM DIG IN

10V/20mA IN

10V/20mA IN

10V OUT

130BB985.10

BUS TER.

OFF

ON

Illustration 1.3 Control Terminals

VLT® HVAC Basic Drive Casca...

VLT

®

 HVAC Basic Drive Cascade Controller

4

MI18I302 - VLT

®

 is a registered Danfoss trademark

1

1

Summary of Contents for VLT HVAC

Page 1: ...MAKING MODERN LIVING POSSIBLE Instruction VLT HVAC Basic Drive Cascade Controller...

Page 2: ......

Page 3: ...is 3 In this operation the run time between pumps is equalized reducing the required pump maintenance and increasing reliability and lifetime of the system The alternation of the lead pump can take p...

Page 4: ...P Coast to stop Cut out correspond relays terminal 27 29 and 42 45 External Interlock Coast to stop Cut out built in relays are de energized Table 1 1 Commands Assigned to Digital Inputs LCP keys Vari...

Page 5: ...he programmed time expires Parameter Range Default Function 25 42 Staging Threshold Expressionlimit 0 100 90 The percentage of maximum pump speed to stage on a fixed speed pump 25 43 Destagi ng Thresh...

Page 6: ...an be reset by writing 0 25 90 Pump Interlock 0 Off 1 On 0 Off Choose the pump to interlock for e g service The pump will be taken out of any pump cycling etc Table 1 3 1 2 Installation 1 2 1 Control...

Page 7: ...PNP Bus ter Bus ter RS 485 Interface RS 485 N PS 485 69 P RS 485 68 Com RS 485 61 PNP Source NPN Sink ON Terminated OFF Unterminated ON 1 2 240V AC 3A Not present on all power sizes Do not connect shi...

Page 8: ...Coated Coated Coated Coated Coated Coated Coated Coated Coated Table 1 4 Frequency Converter P15K P18K P22K P30K P37K P45K P55K P75K P90K Typical shaft output kW 15 18 22 30 37 45 55 75 90 IP20 Frame...

Page 9: ...Digital Outputs 5 30 Terminal 27 Digital Output 5 31 Terminal 29 Digital Output 5 34 On Delay Digital Output 5 35 Off Delay Digital Output 5 4 Relays 5 40 Function Relay 5 41 On Delay Relay 5 42 Off...

Page 10: ...25 06 Number of Pumps 25 2 Bandwidth Settings 25 20 Staging Bandwidth 25 21 Override Bandwidth 25 22 Fixed Speed Bandwidth 25 23 SBW Staging Delay 25 24 SBW Destaging Delay 25 25 OBW Time 25 27 Stage...

Page 11: ...www danfoss com drives MI18I302 130R0267 MI18I302 Rev 2012 08 31...

Reviews: