10 Specifications
10.1 Power-dependent Specifications
Mains Supply 3x380-480 V AC
N110
N132
N160
N200
N250
N315
High/Normal Load*
NO
NO
NO
NO
NO
NO
Typical Shaft output at 400 V
[kW]
110
132
160
200
250
315
Typical Shaft output at 460 V
[hp]
150
200
250
300
350
450
Typical Shaft ouptut at 480 V
[kW]
132
160
200
250
315
355
Enclosure IP21
D1h
D1h
D1h
D2h
D2h
D2h
Enclosure IP54
D1h
D1h
D1h
D2h
D2h
D2h
Enclosure IP20
D3h
D3h
D3h
D4h
D4h
D4h
Output current
Continuous (at 400 V) [A]
212
260
315
395
480
588
Intermittent (60 Sec overload)
(at 400 V)[A]
233
286
347
435
528
647
Continuous (at 460/500 V) [A]
190
240
302
361
443
535
Intermittent (60 sec overload)
(at 460/500 V) [kVA]
209
264
332
397
487
588
Continuous kVA (at 400 V) [kVA]
147
180
218
274
333
407
Continuous kVA (at 460 V) [kVA]
151
191
241
288
353
426
Max. Input current
Continuous (at 400 V) [A]
204
251
304
381
381
463
463
567
Continuous (at 460/500 V) [A]
183
231
291
348
348
427
427
516
Max. cable size: mains, motor,
brake and load share [mm
2
(AWG
2)
)]
5)
2x95
(2x3/0)
2x185
(2x350)
Max. external mains fuses [A]
1
315
350
400
550
630
800
Estimated power loss at 400V
[W]
4
2555
2949
3764
4109
5129
6663
Estimated power loss at 460V
[W]
2257
2719
3622
3561
4558
5703
Weight, enclosure IP21, IP54 kg
(lbs.)
62 (135)
125 (275)
Weight, enclosure IP20 kg (lbs.)
62 (135)
125 (275)
Efficiency
4)
0.98
Output frequency
0-800 Hz
0-600 Hz
*Normal overload = 110% current for 60 Sec.
Table 10.1
1) For type of fuse see
2) American Wire Gauge
3) Measured using 5 m screened motor cables at rated load and rated frequency.
Specifications
VLT
®
HVAC Drive D-Frame
Operating Instructions
58
MG16D102 - VLT
®
is a registered Danfoss trademark
10