frequency converter is no longer blocked and can be reset
once the cause has been rectified.
Alarms that are not trip locked can also be reset using the
automatic reset function in
parameter 14-20 Reset Mode
(Warning: Automatic wake-up is possible.)
If a warning or alarm is marked against a code in
,
this means that either a warning occurs before an alarm, or
it is possible to specify whether a warning or an alarm
should be shown for a given fault.
This is possible, for instance, in
parameter 1-90 Motor
Thermal Protection
. After an alarm or trip, the motor carries
on coasting, and the alarm and warning flash. Once the
problem has been rectified, only the alarm continues
flashing until the frequency converter is reset.
NOTICE
No missing motor phase detection (numbers 30-32) and
no stall detection are active when
parameter 1-10 Motor
Construction
is set to
[1] PM non-salient SPM
.
Number Description
Warning
Alarm/
Trip
Alarm/
Trip Lock
Parameter
Reference
1
10 volts low
X
–
–
2
Live zero error
(X)
(X)
–
Parameter 6-01 Live Zero Timeout Function
3
No motor
(X)
–
–
Parameter 1-80 Function at Stop
4
Mains phase loss
(X)
(X)
(X)
Parameter 14-12 Response to Mains
Imbalance
5
DC-link voltage high
X
–
–
–
6
DC-link voltage low
X
–
–
–
7
DC overvoltage
X
X
–
–
8
DC undervoltage
X
X
–
–
9
Inverter overloaded
X
X
–
–
10
Motor ETR overtemperature
(X)
(X)
–
Parameter 1-90 Motor Thermal Protection
11
Motor thermistor overtemperature
(X)
(X)
–
Parameter 1-90 Motor Thermal Protection
12
Torque limit
X
X
–
–
13
Overcurrent
X
X
X
–
14
Ground fault
X
X
–
–
15
Hardware mismatch
–
X
X
–
16
Short circuit
–
X
X
–
17
Control word timeout
(X)
(X)
–
Parameter 8-04 Control Word Timeout
Function
20
Temp. input error
–
X
–
–
21
Param error
–
X
–
22
Hoist mech. brake
(X)
(X)
–
Parameter group 2-2* Mechanical Brake
23
Internal fans
X
–
–
–
24
External fans
X
–
–
–
25
Brake resistor short-circuited
X
–
–
–
26
Brake resistor power limit
(X)
(X)
–
Parameter 2-13 Brake Power Monitoring
27
Brake chopper short-circuited
X
X
–
28
Brake check
(X)
(X)
–
Parameter 2-15 Brake Check
29
Heat sink temp
X
X
X
30
Motor phase U missing
(X)
(X)
(X)
Parameter 4-58 Missing Motor Phase Function
31
Motor phase V missing
(X)
(X)
(X)
Parameter 4-58 Missing Motor Phase Function
32
Motor phase W missing
(X)
(X)
(X)
Parameter 4-58 Missing Motor Phase Function
33
Inrush fault
X
X
–
34
Fieldbus communication fault
X
X
–
–
35
Option fault
–
–
X
–
36
Mains failure
X
X
–
–
37
Imbalance of supply voltage
X
–
–
38
Internal fault
X
X
–
Maintenance, Diagnostics, a...
User Guide
MG37L202
Danfoss A/S © 08/2017 All rights reserved.
35
6
6